Code
Section |
Location |
Violation Description |
Inspection Date |
Correct By |
Work Order # |
| 807.1 |
Moffett |
Wall hanging over window or room W313 |
1/20/2010 |
2/19/2010 |
Res Life |
| 605.5 |
Moffett |
Extension cord in room W211 |
1/20/2010 |
2/19/2010 |
Res Life |
| 1008.1 |
Moffett |
Decorations covering room entrance door of room E334 |
1/20/2010 |
2/19/2010 |
Res Life |
| 315.2 |
Moffett |
Room W305 |
1/20/2010 |
2/19/2010 |
Res Life |
| 703.1 |
Moffett |
Fire stopping of wall penetrations of fire separation wall located in attic |
1/20/2010 |
2/19/2010 |
Mas 10-04921 |
| 315.2 |
Peery |
Combustible materials not stored properly 162 AD office |
1/20/2010 |
2/19/2010 |
Res Life |
| 703.1.1 |
Peery |
Ceiling tile missing Corridor over 316 |
1/20/2010 |
2/19/2010 |
10-03079 |
| 315.2 |
Trinkle |
Combustible materials not stored properly Room 222 |
1/20/2010 |
2/19/2010 |
|
| 315.2.3 |
Stuart |
Several containers of hydraulic oil and oily rags being stored in B18 elevator room |
1/20/2010 |
2/19/2010 |
Safety |
| 901.4.1 |
Selu |
No smoke detector installed above alarm panel |
1/20/2010 |
2/19/2010 |
Ele |
| 315.2 |
Selu |
Storage of combustibles are not orderly in basement storage room access to the panel is blocked. |
1/20/2010 |
2/19/2010 |
Safety |
| 110.1.1 |
Muse |
Storage of combustible materials on top of and around flammable cabinet located in AA02. Gasoline powered equipment being stored in AA02. |
2/3/2010 |
3/5/2010 |
Res Life |
| 315.2 |
Muse |
Storage of combustible materials in buildings will be orderly Rooms A1318, A1107, A1013, A903, A901, A718, A518, C511, C407, C305, and C302. New notices A1114, A322, and B208 |
2/3/2010 |
3/5/2010 |
Res Life |
| 605.4 |
Muse |
Multi plug adapters in Rooms A912, A823, and B120 |
2/3/2010 |
3/5/2010 |
Res Life |
| 308.3.8 |
Muse |
Open flame producing items in Room A718. New notices in A1314, and C511 |
2/3/2010 |
3/5/2010 |
Res Life |
| 605.4.2 |
Muse |
Re locatable power taps in Room C511. New notices in A1201 and B105. |
2/3/2010 |
3/5/2010 |
Res Life |
| 605.5 |
Muse |
Extension cords in rooms A1201, A1104, A916, A915, A912, A911, A812, A703, C511, C507, C319, and C118. New Notices in A1210 and C305. |
2/3/2010 |
3/5/2010 |
Res Life |
| 1027.3 |
Muse |
Exit sign not illuminated. Not all exit lighting units through the structure connected to generator |
2/3/2010 |
3/5/2010 |
Fac |
| 904.11.6.3 |
Muse |
Accumulation of grease in range hood located behind serving line |
2/3/2010 |
3/5/2010 |
Dinning |
| 904.4.1 |
Muse |
Improper head installed in system protection in kitchen, Cooking equipment located in fire system that has been tagged |
2/3/2010 |
3/5/2010 |
Dinning |
| 605.1 |
Muse |
Electric supply conduit for fire suppression system on hood is not being properly secured |
2/3/2010 |
3/5/2010 |
Dinning |
| 301.3 |
Muse |
No documentation for proper permitting and acceptance testing for fire suppression hood in kitchen |
2/3/2010 |
3/5/2010 |
Dinning |
| 605.3 |
Hurlbert |
Water heater equipment being blocked by storage in Star bucks-storage |
2/10/2010 |
3/12/2010 |
Dinning |
| 703.1.1 |
Bolling |
Hole in ceiling has been improperly patched with plywood in corridor at women's restroom and corridor near room 112 |
2/10/2010 |
3/12/2010 |
Carp 10-04150 |
| 703.1 |
Moffett |
Fire stopping of wall penetrations of fire separations wall located in attic |
2/17/2010 |
3/19/2010 |
10-04921 |
| 315.2 |
Moffett |
Storage of combustible material not orderly W305 |
2/17/2010 |
3/19/2010 |
Res Life |
| 315.2 |
Ingles |
Storage of combustible material not orderly Room 228 |
2/12/2010 |
3/14/2010 |
Res Life |
| 605.5 |
Ingles |
Extension cords in Room 228 |
2/12/2010 |
3/14/2010 |
Res Life |
| 807.1 |
Draper |
Curtains in room 321 |
2/12/2010 |
3/14/2010 |
Res Life |
| 605.5 |
Pocahontas |
Extension cord in room 326 |
2/12/2010 |
3/14/2010 |
Res Life |
| 315.2.1 |
Madison |
Items stored less than 24 inches from ceiling in nonsprinklered area B17 |
2/12/2010 |
3/14/2010 |
RU outdoors |
| 703.1.1 |
Madison |
Ceiling tile missing at corridor at B02 |
2/12/2010 |
3/14/2010 |
Carp |
| 907.20 |
Madison |
Documentation for missing trim ring that was listed on fire report |
2/12/2010 |
3/14/2010 |
Safety |
| 703.1 |
Jefferson |
Fire stop conduits and conduit ends |
2/12/2010 |
3/14/2010 |
Carp |
| 315.2 |
Washington |
Storage of combustibles not orderly in room 330 |
2/12/2010 |
3/14/2010 |
Res Life |
| 807.1 |
Washington |
Curtains in room B11 |
2/12/2010 |
3/14/2010 |
Res Life |
| 703.1 |
Jefferson |
Fire stop conduits and conduit ends in Network Services corridor are not properly applied |
3/24/2010 |
4/23/2010 |
10-06598 |
| 703.2.3 |
Dedmon Center |
Fire rated doors were not self closing and automatic latching: Corridor near 319B, The Highlander room, Main entry Office, Upper level rear Mechanical room, Laundry, Corridor to Pool Area, room 222, room 220, 2nd floor stair at H.C. Door, Pump room under the stair and the Mens and Women's locker rooms to the Pool |
7/23/2010 |
9/21/2010 |
CARP |
| 1027.8 |
Dedmon Center |
Exit door to exterior at the coaches corridor near room 303 requires more than 15lbs to open |
7/23/2010 |
9/21/2010 |
CARP |
| 605.5 |
Dedmon Center |
Extension cords are being used in Mc Cray's,s office, control room at the arena, pool office, team exam room, room 220 to a ref, stage in pool area, and through the roll up door at the chair storage in the arena |
7/23/2010 |
9/21/2010 |
Dedmon Center |
| 605.4.2 |
Dedmon Center |
Relocatable power taps in McCray's office and the Control room in the arena |
7/23/2010 |
9/21/2010 |
Dedmon Center |
| 315.2.3 |
Dedmon Center |
Combustible material are being stored in the upper mechanical room and boiler room 203 |
7/23/2010 |
9/21/2010 |
Dedmon Center |
| 605.6 |
Dedmon Center |
Cover missing on an electrical junction box |
7/23/2010 |
9/21/2010 |
ELE |
| 807.1 |
Dedmon Center |
Cloth wall hanging in room 223 |
7/23/2010 |
9/21/2010 |
Dedmon Center |
| 901.6 |
Dedmon Center |
Sprinkler trim ring missing in office 220 and padlock hung from automatic sprinkler piping in men's locker room to the pool |
7/23/2010 |
9/21/2010 |
PLUM |
| 703.1 |
Dedmon Center |
Fire stopping material has been removed from the metal conduit sleeve through fire rated wall in room 203 |
7/23/2010 |
9/21/2010 |
CARP |
| 605.1 |
Dedmon Center |
Floor outlet has been damage in the arena main entry/exit lobby |
7/23/2010 |
9/21/2010 |
ELE |
| 605.3 |
Dedmon Center |
Electrical panel is blocked in arena concessions stands and in the pump room under the stair |
7/23/2010 |
9/21/2010 |
Dedmon Center |
| 3405.5 |
Dedmon Center |
Alcohol based hand rub dispenser is located above the electrical outlet in the corridor at the entry to the men's locker room |
7/23/2010 |
9/21/2010 |
ELE |
| 703.4 |
Dedmon Center |
Written records were not available to show that fire rated doors are binging inspected and tested |
7/23/2010 |
9/21/2010 |
Safety |
| 604.3.2 |
Dedmon Center |
Written records were not available to show that emergency power generator is being inspected and tested |
7/23/2010 |
9/21/2010 |
Safety |
| 901.6.2 |
Dedmon Center |
Written records were not available to show that sprinklers have been tested |
7/23/2010 |
9/21/2010 |
Safety |
| 907.20.2 |
Dedmon Center |
Written records were not available to show that the fire alarm system is being inspected and tested |
7/23/2010 |
9/21/2010 |
Safety |
| 703.2.2 |
Dedmon Center |
And unapproved hold open device was being used to prop open a fire rated door at the training room on the 1st floor |
7/23/2010 |
9/21/2010 |
Dedmon Center |
| 703.2.3 |
Selu |
Entrance fire door is not closing properly in men's bunk room |
10/28/2010 |
12/12/2010 |
Carp 11-03746 |
| 315.2 |
Calhoun Apartment |
Storage of combustible material not orderly in Rooms E bedroom 1, F bedroom2 and A |
10/21/2010 |
12/5/2010 |
Reslife |
| 907.2.10.1.2 |
Calhoun Apartment |
No documentation form being provided for each suite to record required checks |
10/21/2010 |
12/5/2010 |
Reslife |
| 605.4 |
Calhoun Apartment |
Multiplug adapters in Room F bedroom 1 |
10/21/2010 |
12/5/2010 |
Reslife |
| 605.1 |
Calhoun Apartment |
Bulb installed in lamp exceeds max wattages in Suite A and S bedroom 2. |
10/21/2010 |
12/5/2010 |
Reslife |
| 807.1 |
Calhoun Apartment |
Curtains used in Room S bedroom 2 |
10/21/2010 |
12/5/2010 |
Reslife |
| 308.3.8 |
Calhoun Apartment |
Candle in Suite Q |
10/21/2010 |
12/5/2010 |
Reslife |
| 315.2 |
Norwood |
Storage of combustibles not orderly in rooms 316, 218, and 227 |
10/21/2010 |
12/5/2010 |
Reslife |
| 1028.2 |
Norwood |
Dorm egress restricted om rooms,s 112, 218, 227, and 316 |
10/21/2010 |
12/5/2010 |
Reslife |
| 903.5 |
Norwood |
Sprinkler head trim missing in room 1A |
10/21/2010 |
12/5/2010 |
Facilities |
| 605.3 |
Norwood |
Electric service panel blocked in 3rd floor and 1st floor mechanical rooms |
10/21/2010 |
12/5/2010 |
Facilities |
| 605.1 |
Norwood |
Bulb installed in lamp exceeds max wattage in room 123 |
10/21/2010 |
12/5/2010 |
Reslife |
| 605.5 |
Moffett |
Extension cords in rooms East 304, 312, 325, 327, 334, 230, 226, 220, 219, 217, 207, 205, 117, 119 and West 311, 310, 205, 226 |
10/14/2010 |
11/28/2010 |
Reslife |
| 703.1.1 |
Moffett |
Ceiling tile missing in corridor near room E311 |
10/14/2010 |
11/28/2010 |
Facilities |
| 605.4 |
Moffett |
Multi plug adapters in rooms East 319, 325, 230, 205, 203, 125 and West 310, 128, W119 and ROTC office has 3 adapters |
10/14/2010 |
11/28/2010 |
Reslife |
| 605.4.2 |
Moffett |
Relocatable power taps in rooms East 319, 324, 327, and West 303, 210 and ROTC front desk |
10/14/2010 |
11/28/2010 |
Reslife |
| 907.2.10.1.2 |
Moffett |
Rooms not checking smoke detectors East 312, 320, 323, 325, 324, 220, 217, and West 323, 310, 226, 230, 119 |
10/14/2010 |
11/28/2010 |
Reslife |
| 315.2 |
Moffett |
Storage of combustibles not orderly East 324 and 234 |
10/14/2010 |
11/28/2010 |
Reslife |
| 807.1 |
Moffett |
Shower curtain hung over egress path to door way room E234 |
10/14/2010 |
11/28/2010 |
Reslife |
| 605.5 |
Tyler |
Extension cords in rooms 368, 343, 317, 213, ad 248 |
10/7/2010 |
11/21/2010 |
Reslife |
| 605.4 |
Tyler |
Multiplug adapters in room 368 |
10/7/2010 |
11/21/2010 |
Reslife |
| 1027.5.1 |
Tyler |
Emergency lighting units were not operational during of inspection 3rd floor |
10/7/2010 |
11/21/2010 |
Facilities |
| 703.1.1 |
Tyler |
Cable ran up through and across ceiling grid in room 213. Broken ceiling tile in room 213 and missing in room 152. |
10/7/2010 |
11/21/2010 |
Facilities |
| 605.4.2 |
Tyler |
Relocatable power taps in room 218 |
10/7/2010 |
11/21/2010 |
Reslife |
| 1027.4 |
Tyler |
Exit lighting unit improperly installed near room 251 |
10/7/2010 |
11/21/2010 |
Facilities |
| 605.1 |
Tyler |
Damaged outlet in room 033 |
10/7/2010 |
11/21/2010 |
Facilities |
| 907.2 |
Tyler |
Fire alarm panel is showing trouble |
10/7/2010 |
11/21/2010 |
Facilities |
| 605.4.2 |
Washington |
Relocatable power taps in rooms 338, 208, 213, and 132 |
10/7/2010 |
11/21/2010 |
Reslife |
| 907.2.10.1.2 |
Washington |
Smoke detectors not being checked in rooms 201, 212, and B11 |
10/7/2010 |
11/21/2010 |
Reslife |
| 605.5 |
Washington |
Extension cords in rooms 403, 139, 126, and B11 |
10/7/2010 |
11/21/2010 |
Reslife |
| 605.4 |
Washington |
Multiplug adapters in rooms B39, B17, and B01 office |
10/7/2010 |
11/21/2010 |
Reslife |
| 703.1.1 |
Washington |
Ceiling tile missing in basement elevator lobby |
10/7/2010 |
11/21/2010 |
Facilities |
| 1028.5 |
Washington |
Door covering on room 118 |
10/7/2010 |
11/21/2010 |
Reslife |
| 605.4.2 |
Trinkle |
Relocatable power tap in room 314 |
9/23/2010 |
11/7/2010 |
Reslife |
| 110.1.3 |
Trinkle |
Dorm room egress blocked in rooms 210 and 128. Combustible flyers attached to rated wire glass fire door corridor near room 151 |
9/23/2010 |
11/7/2010 |
Reslife |
| 605.4 |
Trinkle |
Multiplug adapters in room 118 |
9/23/2010 |
11/7/2010 |
Reslife |
| 605.5 |
Trinkle |
Extension cords in room 117 |
9/23/2010 |
11/7/2010 |
Reslife |
| 110.1.3 |
Floyd |
Combustible flyers attached to rated glass fire door in main corridor near room 106 |
9/23/2010 |
11/7/2010 |
Reslife |
| 605.1 |
Floyd |
Lamp bulb max wattage exceeded in rooms 328 and 223 |
9/23/2010 |
11/7/2010 |
Reslife |
| 703.2.3 |
Floyd |
Rated dorm room door not working properly in room 223 |
9/23/2010 |
11/7/2010 |
Facilities |
| 1027.5.1 |
Floyd |
Battery backup power for exit lighting not working |
9/23/2010 |
11/7/2010 |
Facilities |
| 807.1 |
Perry |
Curtain in room 327 |
9/23/2010 |
11/7/2010 |
Reslife |
| 605.5 |
Perry |
Extension cord in room 316 |
9/23/2010 |
11/7/2010 |
Reslife |
| 703.2.3 |
Perry |
Door not operating properly in stairwell near 220 and basement crawl space area |
9/23/2010 |
11/7/2010 |
Facilities |
| 703.1.1 |
Perry |
Ceiling tiles missing in main corridor and in basement. Fire stop wall penetrations in basement and housekeeping storage |
9/23/2010 |
11/7/2010 |
Facilities |
| 605.4 |
Stuart |
Multiplug adapter in room 112 |
9/23/2010 |
11/7/2010 |
Reslife |
| 605.5 |
Stuart |
Extension cord in room 112 |
9/23/2010 |
11/7/2010 |
Reslife |
| 605.1 |
Stuart |
Lamp bulb max wattage exceeded in rooms 327, and 216 |
9/23/2010 |
11/7/2010 |
Reslife |
| 807.1 |
Stuart |
Shower curtain used to block egress in room 226 |
9/23/2010 |
11/7/2010 |
Reslife |
| 703.1.1 |
Stuart |
Ceiling tile missing in room B05 and fire stop penetration of basement housekeeping storage B12 |
9/23/2010 |
11/7/2010 |
Reslife |
| 605.5 |
Ingles |
Extension cord in room 324 |
9/30/2010 |
11/14/2010 |
Reslife |
| 807.1 |
Ingles |
Curtain in room 324 |
9/30/2010 |
11/14/2010 |
Reslife |
| 605.4 |
Ingles |
Multiplug adapter in room 223 |
9/30/2010 |
11/14/2010 |
Reslife |
| 903.5 |
Ingles |
Sprinkler system not tested during inspection |
9/30/2010 |
11/14/2010 |
Facilities |
| 605.1 |
Bolling |
Basement boiler room missing circuit blanks |
9/30/2010 |
11/14/2010 |
Facilities |
| 605.4 |
Bolling |
Multiplug adapters in rooms 106, 215, and 317 |
9/30/2010 |
11/14/2010 |
Reslife |
| 605.5 |
Bolling |
Extension cords in rooms 317, 215, 201, 112 |
9/30/2010 |
11/14/2010 |
Reslife |
| 605.5 |
Pocahontas |
Extension cords in rooms 305, 326, 225, 216, 109, and 114 |
9/30/2010 |
11/14/2010 |
Reslife |
| 907.2 |
Pocahontas |
Attic elevator lobby has smoke detector removed |
9/30/2010 |
11/14/2010 |
Facilities |
| 605.1 |
Pocahontas |
Room 310 lamp exceeded max wattage |
9/30/2010 |
11/14/2010 |
Reslife |
| 605.4 |
Pocahontas |
Multiplug adapter in rooms 326 and 225 |
9/30/2010 |
11/14/2010 |
Reslife |
| 315.2 |
Pocahontas |
Storage of combustible not orderly in room 225 |
9/30/2010 |
11/14/2010 |
Reslife |
| 605.4 |
Draper |
Multi plug adapter in rooms 308, 220, and 211 |
9/30/2010 |
11/14/2010 |
Reslife |
| 605.4.2 |
Draper |
Relocatable power taps in room 316 |
9/30/2010 |
11/14/2010 |
Reslife |
| 605.5 |
Draper |
Extension cords in room 211 |
9/30/2010 |
11/14/2010 |
Reslife |
| |
|
|
|
|
|
| |
|
|
|
|
|