Code
Section |
Location |
Violation Description |
Inspection Date |
Correct By |
Work Order # |
| 605.5 |
Bolling |
Extention Cords will not be substituted for permanent wiring
Rm 317,324 corrected during inspection
|
7-Oct-2008 |
7-Oct-2008 |
res-life |
| 605.5 |
Draper |
Extention Cords will not be substituted for permanent wiring
Rm 224 corrected during inspection
|
7-Oct-2008 |
7-Oct-2008 |
res-life |
| 605.4 |
Draper |
Multi-plug adapters prohibited.
Rm 225,309,326 corrected during inspection.
|
7-Oct-2008 |
7-Oct-2008 |
res-life |
| 605.4 |
Norwood |
Multi-plug adapters prohibited.
Rm 123,224 corrected during inspection
|
14-Oct-2008 |
14-Oct-2008 |
res-life |
605.4 |
Muse |
Multi-plug adapters prohibited.
Rm A1103, Removed during inspection: Rm A913, A802, C504
|
16-Dec-2008 |
corrected
13-May-2009 |
res-life |
807.1 |
Muse |
Wall Hangings must be flame rated or noncombustible.
Removed during inspection: Rm A116, A717, A611, A516, B501, C408, A318, C119
|
16-Dec-2008 |
corrected
13-May-2009 |
res-life |
605.5 |
Muse |
Extention Cords will not be substituted for permanent wiring.
Room A322
|
16-Dec-2008 |
12-June-2009 |
catering |
605.4.2 |
Muse |
Relocatable power taps will be directly connected to permanently installed receptacle.
Room C119
|
16-Dec-2008 |
corrected
13-May-2009 |
res-life |
703.1 |
Muse |
Firestopping, fire resistance rating of structural members must be maintained.
Wall penetrations above range hood in kitchen
|
13-May-2009 |
12-June-2009 |
09-08909
09-00884 |
903.5 |
Muse |
Sprinkler systems will be tested and maintained.
2nd floor trash room, B wing housekeeping closet, dining hall kitchen area heads missing trim rings, unable to provide annual testing report, dirty sprinkler head throughout structure.
|
16-Dec-2008 |
corrected
13-May-2009 |
09-11541 |
703.2.3 |
Muse |
Fire doors must close and latch automatically.
1st floor fitness center entrance doors have had all proper hardware removed and the doors dogged down, the fire rating label has also been removed.
|
16-Dec-2008 |
corrected
13-May-2009 |
facilities |
1027.3 |
Muse |
Exit signs will be illuminated.
Sign in corridor near C132
|
16-Dec-2008 |
corrected
13-May-2009 |
09-11540 |
315.2 |
Muse |
Storage of combustibles,... away from heat sources.
Rm C131, A level -dry storage
|
16-Dec-2008 |
corrected
13-May-2009 |
dining |
906.2 |
Muse |
Portable fire extinguishers will be selected , installed, and maintained.
No K class extinguisher being provided for wet range hood system in dining hall serving area. In office BB12 there is an improper type extinguisher not properly mounted sitting on the floor.
|
16-Dec-2008 |
corrected
13-May-2009 |
dining |
1028.2 |
Muse |
Exit and egress shall not be impeded.
Room access to electrical room blocked by storage, dining hall kitchen stairwell exit blocked by cart, A level outside exit blocked by plywood.
|
16-Dec-2008 |
corrected
13-May-2009 |
dining |
904.11.6.3 |
Muse |
Exhaust hoods must be cleaned of grease as needed and records maintained.
Dining Hall kitchen serving area range hoods
|
16-Dec-2008 |
corrected
13-May-2009 |
dining |
605.3 |
Muse |
Electrical panels must be free of obstruction, 30" wide, 36" deep, and 78" high
A level dry storage
|
16-Dec-2008 |
corrected
13-May-2009 |
dining |
315.2.1 |
Muse |
Storage will be maintained 18" below sprinkler heads.
A level dry storage
|
16-Dec-2008 |
corrected
13-May-2009 |
dining |
605.1 |
Muse |
Identified electrical hazards will be abated.
Temporary lighting units in dining hall corridor, exposed wiring A level, equipment room near jockey pump.
|
16-Dec-2008 |
corrected
13-May-2009 |
facilities |
901.4.1 |
Muse |
Fire protection systems must be installed, tested, and maintained with accordance to the code.
Range hood suppression system in dining hall is tagged non compliant, low pressure and links slow to trip as commented in semi-annual inspection report.
|
16-Dec-2008 |
corrected
13-May-2009 |
dining |
315.2.3 |
Muse |
Combustible material will not be stored in boiler, mechanical, or electrical equipment rooms.
A level Boiler Room
|
16-Dec-2008 |
corrected
13-May-2009 |
housekeeping |
| 1019.1.7 |
Muse |
Stairwell floor number signs.
All stairwells do not have proper floor identification, or they are damaged, not at correct height, and do not indicate the direction of travel properly.
|
7-April-2009 |
01-Sept-2009 |
09-11543 |
| 703.1.1 |
Muse |
Ceiling tiles are damaged or missing
tile missing in kitchen |
13-May-2009 |
12-June-2009 |
|
| 904.5 |
Muse |
Wet chemical extinguishing systems shall be maintained according to NFPA 17A
kitchen range hood doesn't have K class extinguisher, dining/service line k class extinguisher not serviced since6/05
|
13-May-2009 |
12-Jun-2009 |
|
| 904.11.1 |
Muse |
Manual actuation devices shall be located at or near a means of egress, min 10ft max 20ft from exhaust system. |
13-May-2009 |
01-Sept-2009 |
|
| 1027.5.1 |
Selu |
The emergency power system will provide power for no less than 60 minutes and consist of storage batteries.
Kitchen area has an emergency light not operational.
|
13-Jan-2009 |
corrected
13-May-2009 |
09-09500 |
| 907.20 |
Selu |
The maintenance procedures for fire alarms and fire detection systems will be in accordance with Chapter 10 NFPA 72.
Smoke detector has been removed and the panel overridden in basement mech room.
|
13-Jan-2009 |
corrected
13-May-2009 |
09-09500 |
| 1028.2 |
Selu |
Exit accesses,exits, or exit discharges will be maintained free from obstruction or impediment.
Womens dorm outside exit door.
|
13-Jan-2009 |
corrected
13-May-2009 |
09-09501 |
| 605.5 |
704 Howe |
Extention Cords will not be substituted for permanent wiring.
Apt 5- bedroom 1
|
20-Jan-2009 |
19-Feb-2009 |
res-life |
| 315.2.3 |
705 Howe |
Combustibles will not be stored in boilers,mech, or electrical equipment rooms.
Room K-utility closet
|
20-Jan-2009 |
19-Feb-2009 |
facilities |
| |
707 Howe |
No violations found. |
20-Jan-2009 |
|
|
| 304.3.2 |
1015
Calhoun |
40 gallon containers shall be provided with lids, noncombustible or approved combustible. |
13-May-2009 |
01-Sept-2009 |
|
| 304.3.3 |
1015
Calhoun |
Dumpsters shall be stored 5 feet away from combustible walls,openings or roof eaves. |
13-May-2009 |
01-Sept-2009 |
|
| 605.1 |
1015 Calhoun |
Identified electrical hazards will be abated.
Circuit breaker panel missing blank in apt O
|
7-April-2009 |
7-May-2009 |
09-11394
09-00883 |
| |
Stuart |
No violations found. |
3-Feb-2009 |
|
|
| |
Floyd |
No violations found. |
3-Feb-2009 |
|
|
| 703.2.3 |
Peery |
Fire doors must close and latch automatically.
RD office entrance door being wedged open.
|
3-Feb-2009 |
corrected
5-May-2009 |
res-life |
| 605.4 |
Trinkle |
Multi-plug adapters prohibited.
3 way adapter in Rm 302
|
3-Feb-2009 |
5-Mar-2009 |
res-life |
| 605.5 |
Trinkle |
Extention Cords will not be substituted for permanent wiring.
Room 302
|
3-Feb-2009 |
5-Mar-2009 |
res-life |
| 807.1 |
Trinkle |
Wall Hangings must be flame rated or noncombustible.
Sheet over window in Rm 302
|
3-Feb-2009 |
5-Mar-2009 |
res-life |
| 703.2.2 |
Ingles |
Fire rated corridor doors being held open with unapproved devices.
Rooms 111, 121
|
3-Feb-2009 |
corrected
5-May-2009 |
res-life |
| 605.5 |
Madison |
Extention Cords will not be substituted for permanent wiring.
Room 315, 317
|
3-Feb-2009 |
corrected
5-May-2009 |
res-life |
| 605.5 |
Washington |
Extention Cords will not be substituted for permanent wiring.
Room 217, 222
|
3-Feb-2009 |
5-Mar-2009 |
res-life |
| 605.4 |
Washington |
Multi-plug adapters prohibited.
Rm 222
|
3-Feb-2009 |
5-Mar-2009 |
res-life |
| 1027.5.1 |
Washington |
Emergency Power system will provide power for 90 minutes utilizing battery backup, or an on-site generator.
4th floor- corridor exit lighting unit # 22 outside of Rm 404 not working on battery backup. |
3-Feb-2009 |
5-Mar-2009 |
09-10447 |
| 605.4 |
Pocahontas |
Multi-plug adapters prohibited.
Rm 306
|
3-Feb-2009 |
corrected
5-May-2009 |
res-life |
| 901.6 |
Pocahontas |
Smoke detector for access doors must be 4" from the wall.
Detector in the lobby by new access door is not 4" from wall |
3-Feb-2009 |
corrected
5-May-2009 |
09-05828 |
| 1027.1 |
Tyler |
Stairs are non-compliant with USBC for tread and riser dimensions.
Newly installed stairs from the porch of Rm 121 |
10-Feb-2009 |
corrected
5-May-2009 |
facilities |
| 1027.5 |
Tyler |
Emergency Lighting.
Emergency light near Rm 364 not operational. |
10-Feb-2009 |
corrected
5-May-2009 |
09-05824 |
| 703.2.3 |
Tyler |
Fire doors must close and latch automatically.
Doors at Rm 134 not latching |
10-Feb-2009 |
corrected
5-May-2009 |
res-life |
| 605.5 |
Tyler |
Extention Cords will not be substituted for permanent wiring.
Room 322
|
10-Feb-2009 |
corrected
5-May-2009 |
res-life |
| 907.20.2 |
Tyler |
Battery Powered Smoke Detectors.
Detector in Rm 140 is not operational |
10-Feb-2009 |
corrected
5-May-2009 |
safety |
| 703.2.2 |
Tyler |
Fire rated corridor doors being held open with unapproved devices.
Room 134
|
10-Feb-2009 |
corrected
5-May-2009 |
res-life |
| 605.3 |
Tyler |
Electrical panels must be free of obstruction, 30" wide, 36" deep, and 78" high
Panel LME in Equipment Room
|
10-Feb-2009 |
corrected
5-May-2009 |
housekeeping |
| 605.5 |
Jefferson |
Extention Cords will not be substituted for permanent wiring.
Room 203
|
10-Feb-2009 |
corrected
5-May-2009 |
res-life |
| 315.2 |
Moffett |
Storage of Combustibles will be orderly
Art Room, student storage near Rm 117 |
10-Feb-2009 |
corrected
5-May-2009 |
art gallery
res-life |
| 605.1 |
Moffett |
Identified electrical hazards will be abated.
Damaged outlet Rm 204
|
10-Feb-2009 |
corrected
5-May-2009 |
09-07359 |
| 907.2.10.1.2 |
Moffett |
Single or multi-station smoke alarms will be installed and maintained in Groups, R-2, R-3, R-4 and I-1 regardless of occupant load.
Smoke detectors not checked in Rms E305, 227, 204, 205
|
10-Feb-2009 |
corrected
5-May-2009 |
res-life |
| 1028.3 |
Moffett |
A means of egress will be free from obstructions that would prevent its use.
Art Room |
10-Feb-2009 |
corrected
5-May-2009 |
09-07296 |
| 703.1 |
Moffett |
Firestopping, fire resistance rating of structural members must be maintained.
Ceiling tiles missing or damaged in corridor near E 226 and Art Room, Fire stop conduits East Side- Attic Fire Wall, West Side- Attic Fire Wall.
|
10-Feb-2009 |
corrected
5-May-2009 |
09-07360 |
| 315.2.3 |
Moffett |
Combustible material will not be stored in boiler, mechanical, or electrical equipment rooms.
B 127 Mechanical Room
|
10-Feb-2009 |
corrected
5-May-2009 |
09-07358 |
| 315.2.1 |
Moffett |
Storage will be maintained 24" or more below the ceiling in non-sprinkled areas.
Art Room |
10-Feb-2009 |
corrected
5-May-2009 |
art gallery |
| 605.3 |
Tyler |
A Working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height was not provided at panel LME in the Equipment Room.
Circuit breaks not correctly label |
07-Jul-2009 |
06-Aug-2009 |
09-01520 |
| 1019.1.7 |
Muse |
All starwells does not have proper floor identification and/or damaged signage and not at correct heights. Direction of travel is not being illustrated properly. |
07-Jul-2009 |
06-Aug-2009 |
09-11543 |
| 904.5 |
Muse |
Kitchen range hood does not have K class extinguisher provided.
09--0/1SY
Dinning room 1serving line K class extinguisher last required annual service
performed on 06/2005.
Dinning room 1serving line -pizza oven does not have fire protection system
provided.
|
07-Jul-2009 |
06-Aug-2009 |
09-01734 |
| 904.11.1 |
Muse |
Dinning room/serving line pull station for range hood manual fire supression system activation travel distance is located more than 20 feet from range hood. |
07-Jul-2009 |
06-Aug-2009 |
Dinning Service |
| 703.1.1 |
Muse |
Tile missing in kitchen |
07-Jul-2009 |
06-Aug-2009 |
Dinning Service |
| 703.1 |
Muse |
Wall penetration above range hood in kitchen |
07-Jul-2009 |
06-Aug-2009 |
09-08909 |
| 605.3 |
Hurlbert |
Water heater and compressor equipment being blocked by storage in Starbucks storage
Electric service panels being blocked by storage Starbucks - storage, mechanical room corridor, and RU Outdoors (service panel, transformer, washer and dryer equipment). |
24-Jul-2009 |
23-Aug-2009 |
Dinning Service |
| 907.2 |
Hurlbert |
Pull stations being blocked by storage in mechanical room corridor and rear exit in Chick-fil-A kitchen |
24-Jul-2009 |
23-Aug-2009 |
Dinning Service |
| 1008.1.8 |
Hurlbert |
Hasp latch lock installed on entrance door to Chick-ful-A kitchen walkin freezer |
24-Jul-2009 |
23-Aug-2009 |
Facilities |
| 315.2.1 |
Hurlbert |
Storage < 18" away from sprinker in Chick-fil-A kitchen storage and 209A |
24-Jul-2009 |
23-Aug-2009 |
Dinning |
| 901.11.6.4 |
Hurlbert |
Range hood systems in Chick-ful-A kitchen x2, Olo Sushi, and Salsarita's last required service was performed 5/2008 |
24-Jul-2009 |
23-Aug-2009 |
Dinning |
| 904.11.5.2 |
Hurlbert |
Need Class K fire extinguisher in Olo Sushi |
24-Jul-2009 |
23-Aug-2009 |
Dinning |
| 904.11.6.3 |
Hurlbert |
Accumulation of grease in range hoods and on cooking and range equipment in Olo Sushi and Salsarita's |
24-Jul-2009 |
23-Aug-2009 |
Dinning |
| 1027.3 |
Hurlbert |
Exit sign out in Salsarita's |
24-Jul-2009 |
23-Aug-2009 |
ELE 10-00508 |
| 807.1 |
Hurlbert |
Combustible material hanging from ceiling |
24-Jul-2009 |
23-Aug-2009 |
RU Outdoors |
| 703.1.1 |
Hurlbert |
Ceiling tiles damaged in room 209 |
24-Jul-2009 |
23-Aug-2009 |
CARP 10-00509 |
| 315.2.2 |
Hurlbert |
Combustible material being stored in 234A roof access ladder area |
24-Jul-2009 |
23-Aug-2009 |
RU Rec |
| 903.5 |
Hurlbert |
Dirty sprinkler heads in conference rooms 248, 249, and 250
Outside fire department connection has one of it's caps missing
Require quarterly testing and service report advised of sprinker heads with paint on ther in Chick-ful-A, Starbucks, chair storage, and in middle section |
24-Jul-2009 |
23-Aug-2009 |
PLUM 10-00505
Dinning |
| 408.1.1 |
Hurlbert |
Occupant load postings not posted for Auditorium and conference rooms 248, 249, and 250 |
24-Jul-2009 |
23-Aug-2009 |
Facilities |
| 301.3 |
Hurlbert |
RU Outdoors has improper constructed mexxanines |
24-Jul-2009 |
23-Aug-2009 |
RU Outdoors |
| 906.2 |
Hurlbert |
Extingusher cabinets located throughout entire structure are not being labeled or identified |
24-Jul-2009 |
23-Aug-2009 |
Safety |
| 912.4 |
Hurlbert |
Sign missing on outside Fire department connection |
24-Jul-2009 |
23-Aug-2009 |
PLUM 10-00510 |
| 1020.1.6 |
Muse |
All starwells does not have proper floor identification and / or damaged signage and not at correct heights. Direction of travel is not being illustrated properly. |
11-Aug-2009 |
10-Sep-2009 |
Safety |
| 703.1 |
Muse |
Fire suppression system conduit penetrating kitchen range hood |
11-Aug-2009 |
10-Sep-2009 |
MT2 10-00898 |
| 904.5 |
Muse |
Dinning Room / serving line - pizza oven does not have fire protection system provided |
11-Aug-2009 |
10-Sep-2009 |
Dinning |
| 315.2.3 |
Muse |
Combustible storage being improperly stored in B level - electrical equipment room |
11-Aug-2009 |
10-Sep-2009 |
MT2 10-00898 |
| 703.2 |
Muse |
Entrance door to B level - electrical equipment room is missing UL listing tag and has not auto door closing equipment installed. |
11-Aug-2009 |
10-Sep-2009 |
MT2 10-00898 |
| 907.20 |
Muse |
Fire alarm system panel showing trouble alarm for severla operation issues. |
11-Aug-2009 |
10-Sep-2009 |
MT2 10-00898 |
| 605.1 |
Tyler |
Circuit breaker service panel not being correctly labeled, LME panel in equipment room.
Circuit breaker service panel, breaker space knock out has been removed without covering by blank leaving exposed wiring. |
11-Aug-2009 |
10-Sep-2009 |
ELE 10-00896 |
| 703.1.1 |
Tyler |
Ceiling tile missing above circuit breaker service panel LME in equipment room. |
11-Aug-2009 |
10-Sep-2009 |
CARP 10-00897 |
| 1008.1.8 |
Washington Hall |
Control door located in basement area of English department. Requires tow separate key operation to be performed at same time and magnet locks are not connected to the central fire alarm systerm as required to release upon activation of the system. Approval was early granted to lock this door provided only one key operation and magnet lock connected to central fire alarm panel. |
08-Sep-2009 |
08-Oct-2009 |
Carp 10-01777 |
| 304.3.3 |
Calhoun Apartments |
Outside dumpster pad within 5 feet of roof eave |
08-Sep-2009 |
08-Oct-2009 |
Grd 10-01778 |
| 1008.1.8 |
Tyler Hall |
Fire door located between main and covered poarch corridors improperly locked. Magnet locks are not connected to central fire alarm system as required to release upon activation of they system. |
08-Sep-2009 |
08-Oct-2009 |
Carp 10-01776 |
| 605.3 |
Hurlbert Hall |
Water heater and compressor equipment being blocked by storage in Starbucks storage |
08-Sep-2009 |
08-Oct-2009 |
Dinning |
| 315.2.3 |
Hurlbert Hall |
Rags stored in 2nd floor -elevator room |
08-Sep-2009 |
08-Oct-2009 |
Ele 10-01775 |
| 907.2 |
Hurlbert Hall |
Pull stations being blocked by storage in mechanical room corridor and rear exit in Chick-fil-A kitchen storage and 209A |
08-Sep-2009 |
08-Oct-2009 |
Dinning |
| 315.2.1 |
Hurlbert Hall |
Chick-fil-A kitchern storage and 209A |
08-Sep-2009 |
08-Oct-2009 |
Dinning |
| 904.11.6.4 |
Hurlbert Hall |
Range hood systems in Chick-ful-A kitcher x2 OLO-Sushi and Salsarita's last required servic performed 05/2008 |
08-Sep-2009 |
08-Oct-2009 |
Dinning |
| 904.11.5.2 |
Hurlbert Hall |
Provide Class K fire extingusher to Olo Sushi |
08-Sep-2009 |
08-Oct-2009 |
Safety 10-01775 |
| 904.11.6.3 |
Hurlbert Hall |
Accumulations of grease in range hoods and on cooking and range equipment in Chick-fil-A, Olo Sushi, and Salsarita's |
08-Sep-2009 |
08-Oct-2009 |
Dinning |
| 703.1.1 |
Hurlbert Hall |
Damaged tiles in room 209. Ceiling tile out of place in 209A |
08-Sep-2009 |
08-Oct-2009 |
Carp 10-01775 |
| 1027.3 |
Hurlbert Hall |
Exit sign not lit in Salsarita's |
08-Sep-2009 |
08-Oct-2009 |
Ele 10-01775 |
| 903.5 |
Hurlbert Hall |
Required quarterly testign and service report advised of sprinkler heads with paint on them in Chick-ful-A, Starbucks, Chair Storage, and in middle section. |
08-Sep-2009 |
08-Oct-2009 |
Plum 10-01775 |
| 408.1.1 |
Hurlbert Hall |
Assembly area occupant loads not posted for Auditorium and conference rooms 248,249, and 250 |
08-Sep-2009 |
08-Oct-2009 |
Sign |
| 301.3 |
Hurlbert Hall |
RU Outdoors has improper constructed mezzanines |
08-Sep-2009 |
08-Oct-2009 |
RU Outdoor |
| 703.2 |
Muse Hall |
Entrance door to B Level- electrical equipment room is missing UL listing tag and has no auto door closing equipment installed. Doors to 122A weight room are not latch properly on their own. |
08-Sep-2009 |
08-Oct-2009 |
|
| 904.5 |
Muse Hall |
Einning room/ serving line pizza oven does not have fire protection system provided |
08-Sep-2009 |
08-Oct-2009 |
Dinning |
| 315.2.3 |
Muse Hall |
Combustible storage being improperly stored in B level electrical equipemnt room |
08-Sep-2009 |
08-Oct-2009 |
|
| 1027.3 |
Muse Hall |
Rear corridor between kitchens above rear outside exit door exit sign out |
08-Sep-2009 |
08-Oct-2009 |
|
| 904.11.6.4 |
Muse Hall |
Last maintenance and testing of all range suppression systems in both kitchen area were perfored 05-2008 |
08-Sep-2009 |
08-Oct-2009 |
Dinning |
| 1008.1.8.7 |
Muse Hall |
Rear stairwell door of 122A weight room door locked from stairwell. |
08-Sep-2009 |
08-Oct-2009 |
|
| 807.1 |
Bolling Hall |
Curtains in room 104. Wall hangings in rooms 326, 317, 319, and 202 |
25-Sep-2009 |
04-Nov-2009 |
Res life |
| 605.5 |
Bolling Hall |
Extension cords in room 106 |
25-Sep-2009 |
04-Nov-2009 |
Res life |
| 605.1 |
Bolling Hall |
Open exposed junction box in attic near elevator |
25-Sep-2009 |
04-Nov-2009 |
ELE 10-02508 |
| 605.4.2 |
Bolling Hall |
Relocatable power tap in room 211 |
25-Sep-2009 |
04-Nov-2009 |
Res life |
| 907.2 |
Bolling Hall |
No documentation of required annual inspection and testing reports on hand for review at the time of inspection |
25-Sep-2009 |
04-Nov-2009 |
Safety |
| 1027.3 |
Draper Hall |
Exit light out in corridor outsid of room 307 |
25-Sep-2009 |
04-Nov-2009 |
Ele 10-02507 |
| 906.2 |
Draper Hall |
Portable fire extinguisher missing in corridor outside of room |
25-Sep-2009 |
04-Nov-2009 |
Safety |
| 605.4.2 |
Draper Hall |
Relocatable power tap used in room 316 |
25-Sep-2009 |
04-Nov-2009 |
Reslife |
| 807 |
Draper Hall |
Curtians in room 321 Wall hangings in rooms 321, 221, and 220 |
25-Sep-2009 |
04-Nov-2009 |
Reslife |
| 605.4 |
Draper Hall |
Multiplug adapters in rooms 318 and 201 |
25-Sep-2009 |
04-Nov-2009 |
Reslife |
| 605.5 |
Draper Hall |
Extension cords in room 221 |
25-Sep-2009 |
04-Nov-2009 |
Reslife |
| 907.2 |
Draper Hall |
No documentation of required annual inspection and testing reports on hand for review at the time of inspection |
25-Sep-2009 |
04-Nov-2009 |
Safety |
| 605.5 |
Pocahontas |
Extension cord in room 326 |
25-Sep-2009 |
04-Nov-2009 |
Reslife |
| 807.1 |
Pocahontas |
Curtains in room 326 and wall hangings in room 324 |
25-Sep-2009 |
04-Nov-2009 |
Reslife |
| 315.2.2 |
Pocahontas |
Trash can located in stair well near room 114 |
25-Sep-2009 |
04-Nov-2009 |
Reslife |
| 907.2 |
Pocahontas |
No documentation of required annual inspection and testing reports on hand for review at the time of inspection |
25-Sep-2009 |
04-Nov-2009 |
Safety |
| 605.5 |
Ingles |
Extension cord in room 228 |
25-Sep-2009 |
04-Nov-2009 |
Reslife |
| 605.3 |
Ingles |
Items in room 321 infront of electrical equipment |
25-Sep-2009 |
04-Nov-2009 |
Reslife |
| 807.1 |
Ingles |
Wall hangings in room 303 |
25-Sep-2009 |
04-Nov-2009 |
Reslife |
| 907.2 |
Ingles |
No documentation of required annual inspection and testing reports on hand for review at the time of inspection |
25-Sep-2009 |
04-Nov-2009 |
Safety |
| 703.1.1 |
Jefferson |
Celing tile damaged in corridor near B02 |
02-Oct-2009 |
01-Nov-2009 |
CARP 10-02657 |
| 1028.2 |
Jefferson |
Required exit access being blocked by storage in egress of Network Services |
02-Oct-2009 |
01-Nov-2009 |
Network services |
| 703.1 |
Jefferson |
Fire stop conduits and conduit ends in Network services corridor |
02-Oct-2009 |
01-Nov-2009 |
CARP 10-02657 |
| 807.1 |
Norwood |
Wall hangings in rooms 214 and 202 |
02-Oct-2009 |
11-Nov-2009 |
Res life |
| 703.1 |
Norwood |
Fire stop conduits and conduit ends in 2nd floor electrical room and wall penetration 1st floor electrical room |
02-Oct-2009 |
11-Nov-2009 |
CARP 10-02656 |
| 903.5 |
Norwood |
Trim ring around sprinkler head is messing in room 202 bathroom |
02-Oct-2009 |
11-Nov-2009 |
MTZ 10-02656 |
| 807.1 |
Tyler Hall |
Wall hanging in room 348 - commons, 115, and 118 |
02-Oct-2009 |
11-Nov-2009 |
Res life |
| 605.1 |
Tyler Hall |
Cable winr running through celing tiles of rooms of 354 and 350 |
02-Oct-2009 |
11-Nov-2009 |
Res life |
| 605.5 |
Tyler Hall |
Extension cord in room 241 |
02-Oct-2009 |
11-Nov-2009 |
Res life |
| 1028.2 |
Tyler Hall |
Chairs being stored in egress near 245 |
02-Oct-2009 |
11-Nov-2009 |
Res life |
| 1028.5 |
Tyler Hall |
Furnishings obstructing an exit |
02-Oct-2009 |
11-Nov-2009 |
Res life |
| 703.1.1 |
Tyler Hall |
Ceiling tile missing in Corridor at room 162 |
02-Oct-2009 |
11-Nov-2009 |
CARP 10-02658 |
| 907.2 |
Washington |
Maintenance and testing schedules will be in accordance wiht Ch 10 of NFPA 72 |
16-Oct-2009 |
25-Nov-2009 |
ELE 10-03086 |
| 703.1.1 |
Washington |
celining tile missing corridor at 403 and above main fire alarm panel |
16-Oct-2009 |
25-Nov-2009 |
CARP 10-03086 |
| 807.1 |
Washington |
Flags in rooms 338 and 116 and curtains in B01 |
16-Oct-2009 |
25-Nov-2009 |
Res life |
| 308.3.8 |
Washington |
Candles in rooms B01 and B02 |
16-Oct-2009 |
25-Nov-2009 |
Res life |
| 605.5 |
Washington |
Extension cords in rooms B03 and B05 |
16-Oct-2009 |
25-Nov-2009 |
Res life |
| 907.2 |
Peery |
Mainteance and testing of smoke detection system maintenance |
16-Oct-2009 |
25-Nov-2009 |
ELE 10-03079 |
| 315.2 |
Peery |
Storage of combustible items in 162 AD office |
16-Oct-2009 |
25-Nov-2009 |
Res life |
| 315.2.1 |
Peery |
Storage of materials close to sprinkler head |
16-Oct-2009 |
25-Nov-2009 |
Res life |
| 807.1 |
Peery |
Wall hangings in room 160 and Curtains in room 222 and 308 |
16-Oct-2009 |
25-Nov-2009 |
Res life |
| 605.5 |
Peery |
Extension cords in room 308 |
16-Oct-2009 |
25-Nov-2009 |
Res life |
| 703.1.1 |
Peery |
ceiling tile missing in corridor over 316 and B09 |
16-Oct-2009 |
25-Nov-2009 |
CARP 10-03079 |
| 1008.1 |
Peery |
Door decoration placed over room entrance of 201 |
16-Oct-2009 |
25-Nov-2009 |
Res life |
| 907.2 |
Stuart |
Maintenance and testing of detection systems |
16-Oct-2009 |
25-Nov-2009 |
ELE 10-03080 |
| 315.2.3 |
Stuart |
Several containers of hydraulic oil and oily rags being stored in B18 elevator equipment room |
16-Oct-2009 |
25-Nov-2009 |
ELE 10-03080 |
| 807.1 |
Stuart |
flags in room 216 |
16-Oct-2009 |
25-Nov-2009 |
Res life |
| 703.1.1 |
Stuart |
Ceiling tile missing at reception desk |
16-Oct-2009 |
25-Nov-2009 |
Carp 10-03080 |
| 907.2 |
Trinkle |
Smoke detector #28 failed |
16-Oct-2009 |
25-Nov-2009 |
ELE 10-03084 |
| 807.1 |
Trinkle |
Flags in rooms 223 222 and 128 |
16-Oct-2009 |
25-Nov-2009 |
Res life |
| 605.4.2 |
Trinkle |
Plug adapter in room 222 |
16-Oct-2009 |
25-Nov-2009 |
Res life |
| 315.2 |
Trinkle |
combustible improperly stored in room 222 |
16-Oct-2009 |
25-Nov-2009 |
Res life |
| 807.1 |
Floyd |
Wall hangings in room 323 |
16-Oct-2009 |
25-Nov-2009 |
Res life |
| 605.5 |
Floyd |
Extension cords in room 203 |
16-Oct-2009 |
25-Nov-2009 |
Res life |
| 605.4.2 |
Floyd |
plug adapter in room 203 |
16-Oct-2009 |
25-Nov-2009 |
Res life |
| 1008.1 |
Floyd |
Decorations covering room entrance door of 206, 106, and 125 |
16-Oct-2009 |
25-Nov-2009 |
Res life |
| 605.1 |
Floyd |
52 watt bulb has been replaced in a lamp of maximum safety wattage of 40 in room 125 |
16-Oct-2009 |
25-Nov-2009 |
Res life |
| 907.2 |
Madison |
No annual inspection and testing report available on hand at the time of inspection |
16-Oct-2009 |
25-Nov-2009 |
Safety |
| 1027.3 |
Madison |
Exit sign not lit in corridor near 308 and B 39 |
16-Oct-2009 |
25-Nov-2009 |
|
| 315.2.2 |
Madison |
furniture stored in stairwell at room 126 |
16-Oct-2009 |
25-Nov-2009 |
Res life |
| 703.1.1 |
Madison |
Ceiling tile missing in corridor at b level student lounge, at B06, at B02 and near B39 |
16-Oct-2009 |
25-Nov-2009 |
|
| 315.2 |
Madison |
RU outdoors storage, B19 and B17 not orderly |
16-Oct-2009 |
25-Nov-2009 |
Res life |
| 315.2.1 |
Madison |
Storage not below 24 inches of ceiling |
16-Oct-2009 |
25-Nov-2009 |
Res life |
| 304.1 |
Madison |
Storage on top of flammable cabinet in room B17 |
16-Oct-2009 |
25-Nov-2009 |
Res life |
| 605.4.2 |
Madison |
power adapter in room B35 |
16-Oct-2009 |
25-Nov-2009 |
Res life |
| 605.4 |
704 Howe apartments |
Multi plug adapter used |
23-Oct-2009 |
22-Nov-2009 |
Res life |
| 907.2.10.1.2 |
704 Howe apartments |
Single or multiple station smoke alarm will be installed and maintained Room 2 |
23-Oct-2009 |
22-Nov-2009 |
Safety |
| 605.4 |
Moffett |
Multiplug adapters in rooms W121. E125 and W211 |
23-Oct-2009 |
02-Dec-2009 |
Res life |
| 605.5 |
Moffett |
Extension cords in rooms W121, W108, and E120 |
23-Oct-2009 |
02-Dec-2009 |
Res life |
| 807.1 |
Moffett |
Wall hangings in rooms E127, E221, W219, W303, and W313 Curtains in rooms E108, E203, and E305 |
23-Oct-2009 |
02-Dec-2009 |
Res life |
| 605.4.2 |
Moffett |
Relocatable power tap in E108 |
23-Oct-2009 |
02-Dec-2009 |
Res life |
| 907.2.10.1.2 |
Moffett |
Smoke detectors not tested in E221, E232, W221, W219, W303, W322, and E305 |
23-Oct-2009 |
02-Dec-2009 |
Res life |
| 703.1.1 |
Moffett |
Ceiling tiles missing or damaged in rooms E232 and E328 |
23-Oct-2009 |
02-Dec-2009 |
Carp 10-03258 |
| 1008.1 |
Moffett |
Decorations covering room entrance door of room W232 |
23-Oct-2009 |
02-Dec-2009 |
Res life |
| 315.2 |
Moffett |
Comustible materials stored improperly in room W305 and in attic |
23-Oct-2009 |
02-Dec-2009 |
Res life |
| 605.3 |
Moffett |
Blocking electrical service equipment |
23-Oct-2009 |
02-Dec-2009 |
ELE 10-03259 |
| 703.1 |
Moffett |
Fire stop wall penetrations not installed |
23-Oct-2009 |
02-Dec-2009 |
ELE 10-03260 |
| |
|
|
|
|
|
| |
|
|
|
|
|