RADFORD UNIVERSITY
FIRE SAFETY INSPECTIONS - STATE FIRE MARSHAL
2005
DATE |
STATUS |
BLDG |
LOCATION |
VIOLATION |
TO |
W/O # |
05-04-05 01-19-06 01-31-06 |
open open closed |
Bolling | Building | some smoke/heat detectors failed inspection | Facilities |
14427 |
10-31-05 01-19-06 01-31-06 |
open open closed |
Bolling | stair at rm 205, hall at rm 307, attic | smoke detector failed inspection | Facilities |
|
10-31-05 11-15-05 01-19-06 |
open open closed |
Bolling | fire alarm panel | backup batteries need replacing | Facilities |
06-07874 |
11-15-05 01-19-06 |
open closed |
Bolling | elevator | light fixture damaged | Facilities |
06-07875 |
11-15-05 01-19-06 |
open closed |
Bolling | elevator shaft | penetrations not properly fore stopped | Facilities |
06-07876 |
05-04-05 01-19-06 |
open closed |
Draper | Building | some smoke/heat detectors failed inspection | Facilities |
14434 |
10-31-05 11-15-05 01-19-06 |
open open closed |
Draper | fire alarm panel | backup batteries need replacing | Facilities |
06-07877 |
10-31-05 01-19-06 |
open closed |
Draper | basement kitchen closet, rm 203, hall at rm 219, back elevator | smoke detector failed inspection | Facilities |
|
11-15-05 01-31-06 04-25-06 06-07-06 |
open closed open closed |
Draper | attic near elevator | heat detector not mounted correctly | Facilities | 06-09877 |
5-04-05 01-19-06 |
open closed |
Floyd | Building | sprinkler system violations | Facilities |
|
10-31-05 01-19-06 |
open closed |
Floyd | fire alarm panel | backup batteries need replacing | Facilities |
|
10-31-05 01-19-06 |
open closed |
Floyd | hall at restrooms | smoke detector failed inspection | Facilities |
|
11-08-05 01-19-06 01-26-06 |
open open closed |
Floyd | sprinklers | inspection records not available | Facilities |
|
11-08-05 01-19-06 |
open closed |
Floyd | exit signs, emergency lights | inspection records not available | Safety |
|
11-08-05 01-19-06 01-26-06 |
open open closed |
Floyd | basement mechanical room | fire alarm junction box improperly mounted | Facilities |
|
11-08-05 01-19-06 01-31-06 |
open open closed |
Floyd | sprinkler riser room | resistor not installed in junction box | Facilities |
|
11-08-05 01-19-06 01-26-06 |
open open closed |
Floyd | rm B03 | improper storage | Res Life |
|
05-04-05 01-19-06 03-21-06 |
open open closed |
Ingles | Building | sprinkler system violations | Facilities |
|
10-31-05 11-15-05 01-19-06 |
open open closed |
Ingles | fire alarm panel | backup batteries need replacing | Facilities |
06-07867 |
10-31-05 11-15-05 01-19-06 01-31-06 |
open open closed open closed |
Ingles | air duct at elevator side | smoke detector failed inspection | Facilities |
06-07867 |
11-15-05 01-19-06 |
open closed |
Ingles | sprinkler box and water heater | open outlet | Facilities |
06-07868 |
11-15-05 01-19-06 |
open closed |
Ingles | elevator lobby | ceiling finished not maintained | Facilities |
06-07869 |
11-15-05 01-19-06 01-31-06 03-21-06 04-25-06 06-07-06 07-17-06 |
open open open open open open closed |
Ingles | fire alarm panel | trouble light on | Facilities |
06-07870 |
11-15-05 01-19-06 01-25-06 01-31-06 03-21-06 04-25-06 |
open open closed open open closed |
Ingles | mech closets floors 2 & 3 | wall not complete above door | Facilities |
06-07871 |
11-15-05 01-19-06 01-25-06 01-31-06 03-21-06 |
open open closed open closed |
Ingles | rm 125 | fire door not maintained | Facilities |
06-07872 |
11-15-05 01-19-06 01-25-06 01-31-06 03-21-06 04-25-06 06-07-06 |
open open closed open open open closed |
Ingles | rm 323 | fire door not being maintained | Facilities | |
11-15-05 01-19-06 |
open closed |
Ingles | Network rm 2nd floor | extension cord | Network Serv |
|
11-15-05 01-19-06 01-25-06 01-31-06 03-21-06 |
open open closed open closed |
Ingles | hall at rm 111 (#9) | exit sign backup out | Facilities |
06-07873 |
02-23-05 |
closed | Jefferson | throughout building | no documentation for flame resistant fabrics | Res Life |
|
02-23-05 |
closed | Jefferson | rms 311, 309, 122, 120, 113, 111 |
multi-plug adapters | Res Life |
|
02-23-05 |
closed | Jefferson | rms 120, 108 | powerstrips connected to each other | Res Life |
|
02-23-05 05-04-05 |
closed | Jefferson | rm 308 | powerstrips connected to each other | Res Life |
|
02-23-05 |
closed | Jefferson | hall outside network services | wall penetrations | Facilities |
|
02-23-05 |
closed | Jefferson | rms 227, 231, 109 | extension cords | Res Life |
|
02-23-05 05-04-05 |
open closed |
Jefferson | 16 rooms | no weekly records for smoke detectors | Res Life |
|
05-04-05 05-17-05 |
open closed |
Jefferson | Building | some smoke/heat detectors failed inspection | Facilities |
14435 |
10-31-05 11-29-05 01-19-06 |
open open closed |
Jefferson | fire alarm panel | backup batteries need replacing | Facilities |
06-08308 |
11-29-05 01-19-06 01-25-06 |
open open closed |
Jefferson | rm123 | multi plug extension cord | Res Life |
|
11-29-05 01-19-06 01-25-06 |
open open closed |
Jefferson | building | daisy chaining power taps | Res Life |
|
11-29-05 01-19-06 01-31-06 03-21-06 04-25-06 |
open closed open open closed |
Jefferson | network services (telephone services?) | outlets not covered | Facilities |
06-08309 06-08311 |
11-29-05 01-19-06 01-25-06 |
open open closed |
Jefferson | network services | openings in electrical panel | Facilities |
06-08309 |
11-29-05 01-19-06 |
open closed |
Jefferson | rm 110, 130 | outlets not working properly | Facilities |
06-08311 |
11-29-05 01-19-06 01-25-06 01-31-06 |
open closed open open closed |
Jefferson | res life storage rm basement | penetrations not fire stopped | Facilities |
06-08312 |
01-20-05 |
closed | Madison | rm 327 | smoke detectors, no weekly records | Facilities |
|
01-20-05 |
closed | Madison | rm 321 | no documentation for flame resistant fabrics | Facilities |
|
01-20-05 |
closed | Madison | rm 121 | extension cords | Res Life |
|
01-20-05 01-19-06 |
open closed |
Madison | basement lounge stairwell | fire doors do not latch automatically | Facilities |
11093 |
05-04-05 05-17-05 |
open closed |
Madison | Building | some smoke/heat detectors failed inspection | Facilities |
14436 |
10-31-05 12-06-05 01-19-06 |
open open closed |
Madison | fire alarm panel | backup batteries need replacing | Facilities |
06-08577 |
10-31-05 12-06-05 01-19-06 |
open open closed |
Madison | stair at rm 108 | smoke detector failed inspection | Facilities |
06-08577 |
12-06-05 01-19-06 01-25-06 |
open open closed |
Madison | stair near rm 228 | fire door assembly not being maintained | Facilities |
06-08582 |
12-06-05 01-19-06 01-25-06 02-14-06 |
open closed open closed |
Madison | mech rm | elev shaft not fire stopped | Facilities |
06-08583 |
12-06-05 01-19-06 01-25-06 |
open open closed |
Madison | RU Outdoors office | light fixture not mounted properly | Facilities |
06-08584 |
12-06-05 01-19-06 01-25-06 02-14-06 04-25-06 |
open open open open closed |
Madison | Office B-15 | being used as storage rm | Res Life |
|
12-06-05 01-19-06 01-25-06 02-14-06 04-25-06 |
open open open open closed |
Madison | basement stair door | wood paneling | Facilities |
Doug |
12-06-05 01-19-06 01-25-06 02-14-06 04-25-06 |
open open open open closed |
Madison | basement | flame spread rating on paneling not verified | Facilities |
Doug |
01-20-05 |
closed | Moffett | attic | fire doors do not latch automatically | Facilities |
|
02-23-05 |
closed | Moffett | attic | fire doors do not latch automatically | Facilities |
|
04-06-05 |
closed | Moffett | E305, E316, E322, E204, W333,W209, W110 | extension cords | Res Life |
|
04-06-05 05-04-05 |
open closed |
Moffett | W227, W110 | extension cords | Res Life |
|
04-06-05 01-19-06 |
open closed |
Moffett | E329, W221, E228, E222, E124 | powerstrips connected | Res Life |
|
04-06-05 05-04-05 |
open closed |
Moffett | W321 | powerstrips connected | Res Life |
|
04-06-05 |
closed | Moffett | by W328 and by W209 | fire doors do not latch automatically | Facilities |
14645 |
04-06-05 |
closed | Moffett | 21 rooms | smoke detector not being tested weekly | Res Life |
|
04-06-05 05-04-05 |
open closed |
Moffett | 26 rooms | smoke detector not being tested weekly | Res Life |
|
04-06-05 |
closed | Moffett | W215, E122, W119, utility rm student health |
multi plug adapters | Res Life |
|
04-06-05 05-04-05 |
open closed |
Moffett | W215 | multi plug adapters | Res Life |
|
05-04-05 01-19-06 |
open closed |
Moffett | Building | some smoke/heat detectors failed inspection | Facilities |
14438 |
10-31-05 12-06-05 01-19-06 |
open open closed |
Moffett | fire alarm panel | backup batteries need replacing | Facilities |
06-08549 |
10-31-05 12-06-05 01-19-06 |
open open closed |
Moffett | hall at rm 227E | smoke detector failed inspection | Facilities |
06-08549 |
12-06-05 01-19-06 |
open closed |
Moffett | stair student health | pull station needs to be removed | Facilities |
06-08549 |
12-06-05 01-19-06 |
open closed |
Moffett | 3rd fl west kitchen | damaged heat detector | Facilities |
06-08549 |
12-06-05 01-19-06 |
open closed |
Moffett | 3rd fl west vending area | smoke detector not secured | Facilities |
06-08549 |
12-06-05 01-19-06 01-25-0 02-14-06 03-21-06 04-25-06
|
open open open open open closed
|
Moffett | mech rm in health serv near stair | no light fixture | Facilities |
06-08550 |
12-06-05 01-19-06 01-25-06 |
open open closed |
Moffett | mech rm student health | trash being stored | Facilities |
06-08551 |
12-06-05 01-19-06 01-25-06 |
open open closed |
Moffett | exam rm 4 | extension cords | St Health |
|
12-06-05 01-19-06 |
open closed |
Moffett | stair at E. side elev equip rm | exit sign backup out | Facilities |
06-08552 |
12-06-05 01-19-06 02-14-06 03-21-06 |
open closed open closed |
Moffett | near rm E110 | exit sign backup out | Facilities |
06-08552 |
12-06-05 01-19-06 02-14-06 03-21-06 |
open closed open closed |
Moffett | attic east & west elevator shaft | penetrations not fire stopped | Facilities |
06-08553 |
12-06-05 01-19-06 02-14-06 03-21-06 |
open closed open closed |
Moffett | student rec rm | open junction boxes | Facilities |
06-08554 |
12-06-05 01-19-06 02-14-06 03-21-06 04-25-06 |
open closed open open closed |
Moffett | attic center section on the west end dormer | open junction boxes | Facilities | 06-08554 |
12-06-05 01-19-06 01-25-06 2-14-06 03-21-06 04-25-06 |
open open open open open closed |
Moffett | halls 1,2,3 | fire door hardware not being maintained | Facilities |
06-08565 |
12-05-05 01-19-06 01-25-06 |
open open closed |
Moffett | kitchen area | fire ext not tagged | Res life |
|
04-18-05 |
closed | Muse | Main panel | panel in trouble mode | Facilities |
|
04-18-05 |
closed | Muse | A1017, A902, C509, B412, B309 | powerstrips connected | Res Life |
|
04-18-05 |
closed | Muse | A801, A502, B109 | no documentation for flame resistant fabrics | Res Life |
|
04-18-05 |
closed | Muse | A701, B500, B410, C221, C231 | extension cords | Res Life |
|
04-18-05 |
closed | Muse | A701, A715, B410, C309 | multi-plug adapters | Res Life |
|
04-18-05 |
closed | Muse | A701, penthouse meeting rm | damaged outlets | Facilities |
|
04-18-05 |
closed | Muse | A204 trash chute | door not closing | Facilities |
|
04-18-05 06-09-05 07-21-05 01-19-06 |
open open open closed |
Muse | 11th floor stairwell | standpipe missing valve handle | Facilities |
15237 |
04-18-05 |
closed | Muse | 4th floor stairwell by rm B412 | cap missing from standpipe connection | Facilities |
issued |
05-04-05 01-19-06 |
open closed |
Muse | Building | some smoke/heat detectors failed inspection | Facilities |
14440 |
10-31-05 01-19-06 |
open closed |
Muse | fire alarm panel | backup batteries need replacing | Facilities |
|
10-31-05 01-19-06 |
open closed |
Muse | rm B210, 219, C404 | smoke detector failed inspection | Facilities |
|
| 06-07-06 | open | Muse | Building | maufacturer's recalled sprinkler heads | Facilities | |
02-23-05 05-04-05 |
open closed |
Norwood | 2nd floor hskp closet | exposed wiring | Facilities |
15807 |
02-23-05 01-19-06 |
open closed |
Norwood | hall by rm 210 | EM light battery backup not working | Facilities |
|
05-04-05 01-19-06 |
open closed |
Norwood | Building | some smoke/heat detectors failed inspection | Facilities |
14441 |
10-31-05 11-29-05 01-19-06 |
open open closed |
Norwood | fire alarm panel | backup batteries need replacing | Facilities |
06-08303 |
10-31-05 11-29-05 01-19-06 |
open open closed |
Norwood | rm 224 | smoke detector failed inspection | Facilities |
06-08303 |
11-29-05 01-19-06 01-31-06 03-21-06 04-25-06 |
open closed open open closed |
Norwood | door to attic | fire door not latching | Facilities |
06-08304 |
11-29-05 01-19-06 01-25-06 03-21-06 |
open closed open closed |
Norwood | electrical closets floors 2,3 | open penetrations | Facilities |
06-08306 |
11-29-06 01-19-06 01-25-06 01-31-06 03-21-06 |
open open open open closed |
Norwood | 2nd floor electrical closet, basement stair door, elev equip room | fire rated wall not being maintained | Facilities | 06-08306 |
11-29-05 01-19-06 01-31-06 03-21-06 04-25-06 06-07-06 |
open closed open open open closed |
Norwood | 3rd floor stairs, rm 116, 122, 126 | sprinkle heads damaged | Facilities |
06-08307 |
11-29-05 01-19-06 01-25-06 01-31-06 03-21-06 |
open open open open closed |
Norwood | 1st floor electr equip rm | storage | ||
05-04-05 01-19-06 |
open closed |
Peery | Building | sprinkler system violations | Facilities |
|
10-31-05 01-19-06 |
open closed |
Peery | fire alarm panel | backup batteries need replacing | Facilities |
|
11-08-05 01-19-06 01-31-06 03-21-06 04-25-06 06-07-06 07-17-06 |
open closed open open open open open |
Peery | sprinklers | inspection records not available, not being maitained according to code | Facilities |
|
11-08-05 01-19-06 |
open closed |
Peery | exit signs, emergency lights | inspection records not available | Safety |
|
11-08-05 01-19-06 01-26-06 01-31-06 03-22-06 04-25-06 |
open open closed open open closed |
Peery | hskp closets 2nd and 3rd floors | fire stopping not being maintained | Facilities |
|
11-08-05 01-19-06 01-26-06 |
open open closed |
Peery | surface mounted conduit rm 205 | not completed | Facilities |
|
11-08-05 01-19-06 01-26-06 |
open open closed |
Peery | decorative materials on door of rm 114 | no documentation to verify material is flame resistant | Res Life |
|
11-08-05 01-19-06 01-26-06 |
open open closed |
Peery | fire rated door at elevator equipment rm | assembly not maintained properly | Facilities |
|
11-08-05 01-19-06 01-26-06 01-31-06 03-21-06 |
open open open open closed |
Peery | elevator equipment rm sprinkler piping | fire stopping not complete | Facilities |
06-07690 |
11-08-05 01-19-06 01-26-06 |
open open closed |
Peery | rm B10 | light fixture improperly mounted | Facilities |
|
11-08-05 01-19-06 01-26-06 |
open open closed |
Peery | crawl space | improper storage | Facilities |
|
01-20-05 |
closed | Pokie | equipment room in basement | open wiring | Facilities |
|
05-04-05 01-19-06 |
open closed |
Pokie | Building | some smoke/heat detectors failed inspection | Facilities |
14442 |
10-31-05 11-15-05 01-19-06 |
open open closed |
Pokie | fire alarm panel | backup batteries need replacing | Facilities |
06-07861 |
10-31-05 01-19-06 |
open closed |
Pokie | 1st floor lounge | smoke detector failed inspection | Facilities |
|
11-15-05 01-19-06 |
open closed |
Pokie | exit sign near rm 205 | backup out | Facilities |
06-07862 |
11-15-05 01-19-06 |
open closed |
Pokie | Study Lounge basement | damaged outlet | Facilities |
06-07863 |
01-20-05 05-04-05 |
open closed |
Stuart | 1st floor near rm 109 | fire doors do not latch automatically | Facilities |
11092 |
02-23-05 |
closed | Stuart | by room 109 | fire doors do not latch automatically | Facilities |
|
01-20-05 |
closed | Stuart | rm 119 | powerstrips connected to each other | Res Life |
|
05-04-05 01-19-06 |
open closed |
Stuart | Building | sprinkler system violations | Facilities |
|
10-31-05 01-19-06 |
open closed |
Stuart | fire alarm panel | backup batteries need replacing | Facilities |
|
10-31-05 01-19-06 |
open closed |
Stuart | hall at rm 217 | smoke detector failed inspection | Facilities |
|
11-08-05 01-19-06 01-31-06 03-21-06 |
open closed open closed |
Stuart | sprinklers | inspection records not available | Facilities |
|
11-08-05 01-19-06 |
open closed |
Stuart | exit signs, emergency lights | inspection records not available | Facilities |
|
11-08-05 01-19-06 01-26-06 03-21-06 |
open closed open closed |
Stuart | sprinkler top of stairs | painted | Facilities |
06-07696 |
11-08-05 01-19-06 01-26-06 03-21-06 |
open closed open closed |
Stuart | hall rm 317 | ceiling not maintained | Facilities |
06-07696 |
11-08-05 01-19-06 |
open closed |
Stuart | exit sign in hall near rm 220 | damaged | Facilities |
|
11-08-05 01-19-06 01-26-06 |
open open closed |
Stuart | exit sign in basement near elevator | turned in wrong direction | Facilities |
|
11-08-05 01-19-06 01-26-06 |
open open closed |
Stuart | fire doors rm 218, B01 | not self closing and latching | Facilities |
|
11-08-05 01-19-06 01-26-06 01-31-06 03-21-06 04-25-06 |
open closed open open open closed |
Stuart | surface mounted conduit rm B04 | corner covers removed | Facilities |
06-07700 |
11-08-05 01-19-06 01-26-06 01-31-06 03-21-06 04-25-06 |
open open open closed open closed |
Stuart | light fixture rm B10 | improperly mounted | Facilities |
|
11-08-05 01-19-06 01-26-06 03-21-06 |
open open open closed |
Stuart | crawl space | unapproved storage | Facilities |
06-07702 |
01-20-05 |
closed | Tyler | rm 368 | extension cord | Res Life |
|
01-20-05 |
closed | Tyler | rms 210 | extension cord | Res Life |
|
01-20-05 |
closed | Tyler | network rm across from rm 317, electrical rm in basement | ceiling finish not maintained | Facilities |
08484 |
01-20-05 |
closed | Tyler | rms 152, 125 | no documentation for flame resistant fabrics | Res Life |
|
02-23-05 01-19-06 03-21-06 |
closed open closed |
Tyler | network rm by rm 317 | ceiling finish not maintained | Facilities |
|
10-31-05 11-29-05 01-19-06 |
open open closed |
Tyler | fire alarm panel | backup batteries need replacing | Facilities |
06-08295 |
10-31-05 11-29-05 01-19-06 |
open open closed |
Tyler | rm 134, section 2 of the attic | smoke detector failed inspection | Facilities |
06-08259 |
11-29-05 01-19-06 |
open closed |
Tyler | basement mech rm | emerg light not working | Facilities |
06-08296 |
11-29-05 01-19-06 01-25-06 01-31-06 03-21-06 04-25-06 |
open open open open open closed |
Tyler | rm 364 | open penetrations | Facilities |
06-09998 |
11-29-05 01-19-06 01-25-06 03-21-06 |
open open open closed |
Tyler | hskp closet at laundry | open penetrations | Facilities |
06-09998 |
11-29-05 01-19-06 01-25-06 01-31-06 03-21-06 04-25-06 |
open open open open open closed |
Tyler | above hall fire rated doors all floors | open penetrations | Facilities | 06-09998 |
11-29-05 01-19-06 01-25-06 01-31-06 03-21-06 04-25-06 06-07-06 07-17-06 |
open closed open open open open open closed |
Tyler | electrical panels 3BSEC1 and 3BSEC2 | not labeled properly | Facilities |
06-08297 |
11-29-05 01-19-06 |
open closed |
Tyler | basement equip rm | openings in electric panel | Facilities |
06-08298 |
11-29-05 01-19-06 01-31-06 03-21-06 04-25-06 |
open closed open open closed |
Tyler | mech equip rm ceiling | open junction box | Facilities |
06-08298 |
11-29-05 01-19-06 01-25-06 03-21-06 |
open closed open closed |
Tyler | rm 216 | no doc to verify decorative mat are non-combust | Res Life |
|
11-29-05 01-19-06 01-25-06 01-31-06 03-21-06 04-25-06 |
open open open open open closed |
Tyler | rm 262 | storage not orderly | Res Life |
|
11-29-05 01-19-06 01-25-06 03-21-06 |
open closed open closed |
Tyler | fire alarm panel rm, rm 103, rm 026 | ceiling finish not maintained | Facilities |
06-08299 |
11-29-05 01-19-06 01-25-06 01-31-06 03-21-06 |
open open closed open closed |
Tyler | RD apt | barrel bolt on egress door | Res Life |
|
01-20-05 02-23-05 05-04-05 |
open open closed |
Washington | by room 206 | fire doors do not latch automatically | Facilities |
|
01-20-05 02-23-05 |
open closed |
Washington | rms 333, 233, 139, 133 | smoke detectors, no weekly records | Res Life |
|
05-04-05 05-17-05 |
open closed |
Washington | Building | some smoke/heat detectors failed inspection | Facilities |
14446 |
10-31-05 12-06-05 01-19-06 |
open open closed |
Washington | fire alarm panel | backup batteries need replacing | Facilities |
06-08546 |
10-31-05 01-19-06 |
open closed |
Washington | B level laundry | heat detector failed inspection | Facilities |
|
12-06-05 01-19-06 01-24-06 |
open open closed |
Washington | exit signs #19, 17, 3,5,7 | backup power out | Facilities |
06-08547 |
12-06-05 01-19-06 01-24-06 |
open open closed |
Washington | across from rm 120 | storage not orderly | Res Life |
|
12-06-05 01-19-06 01-24-06 |
open open closed |
Washington | stair across from basement elev | fire door assembly | Facilities |
06-08548 |
12-06-05 01-19-06 02-14-06 04-26-06 06-07-06 |
open open open open closed |
Washington | basement English Dept | flame spread rating on paneling not verified | ||
03-23-05 |
|
702 Fairfax | no violations noted | |||
03-23-05 |
closed | 704 Fairfax | Apt A | smoke detector not tested weekly | Res Life |
|
03-23-05 |
closed | 714 Downey | EMS | fire extinguisher not inspected | ||
03-23-05 |
closed | 714 Downey | EMS | smoke detector missing | ||
03-23-05 |
closed | 714 Downey | EMS | outlet cover plate missing | Facilities |
14129 |
03-23-05 |
closed | 714 Downey | Apt D | extension cord | Res Life |
|
03-23-05 |
closed |
1015 Calhoun | Apt H, J, N, M, R, C | open floor/ceiling penetrations | Facilities |
14126 |
03-23-05 |
closed | 1015 Calhoun | Apt H | multi-plug adapter | Res Life |
|
03-23-05 |
closed | 1015 Calhoun | Apt B,K | powerstrips connected | Res Life |
|
03-23-05 |
closed | 1015 Calhoun | Apt Q | extension cord | Res Life |
|
03-23-05 |
closed | 1015 Calhoun | Apt Q | open spaces in electrical panel | Facilities |
14127 |
03-23-05 |
closed | 1015 Calhoun | Apt A | outlet cover plate missing | Facilities |
14128 |
03-23-05 |
closed | 1015 Calhoun | Apt A | smoke detector not tested weekly | Res Life |
|
03-23-05 06-9-05 07-21-05 01-19-06 02-28-06 |
open open open open closed |
Selu | fire alarm panel | Fire alarm panel in trouble mode | Facilities |
14125 16744 |
10-31-05 01-19-06 02-28-06 |
open open closed |
Selu | fire alarm panel | backup batteries need replacing | Facilities |
|
10-31-05 01-19-06 02-28-06 |
open open closed |
Selu | upstairs top stairwell | smoke detector failed inspection | Facilities |
|