RADFORD UNIVERSITY

FIRE SAFETY INSPECTIONS - STATE FIRE MARSHAL

2005

DATE
STATUS
BLDG
LOCATION
VIOLATION
TO
W/O #

05-04-05

01-19-06

01-31-06

open

open

closed

Bolling Building some smoke/heat detectors failed inspection
Facilities
14427

10-31-05

01-19-06

01-31-06

open

open

closed

Bolling stair at rm 205, hall at rm 307, attic smoke detector failed inspection
Facilities
 

10-31-05

11-15-05

01-19-06

open

open

closed

Bolling fire alarm panel backup batteries need replacing
Facilities
06-07874

11-15-05

01-19-06

open

closed

Bolling elevator light fixture damaged
Facilities
06-07875

11-15-05

01-19-06

open

closed

Bolling elevator shaft penetrations not properly fore stopped
Facilities
06-07876

05-04-05

01-19-06

open

closed

Draper Building some smoke/heat detectors failed inspection
Facilities
14434

10-31-05

11-15-05

01-19-06

open

open

closed

Draper fire alarm panel backup batteries need replacing
Facilities
06-07877

10-31-05

01-19-06

open

closed

Draper basement kitchen closet, rm 203, hall at rm 219, back elevator smoke detector failed inspection
Facilities
 

11-15-05

01-31-06

04-25-06

06-07-06

open

closed

open

closed

Draper attic near elevator heat detector not mounted correctly Facilities 06-09877

5-04-05

01-19-06

open

closed

Floyd Building sprinkler system violations
Facilities
 

10-31-05

01-19-06

open

closed

Floyd fire alarm panel backup batteries need replacing
Facilities
 

10-31-05

01-19-06

open

closed

Floyd hall at restrooms smoke detector failed inspection
Facilities
 

11-08-05

01-19-06

01-26-06

open

open

closed

Floyd sprinklers inspection records not available
Facilities
 

11-08-05

01-19-06

open

closed

Floyd exit signs, emergency lights inspection records not available
Safety
 

11-08-05

01-19-06

01-26-06

open

open

closed

Floyd basement mechanical room fire alarm junction box improperly mounted
Facilities
 

11-08-05

01-19-06

01-31-06

open

open

closed

Floyd sprinkler riser room resistor not installed in junction box
Facilities
 

11-08-05

01-19-06

01-26-06

open

open

closed

Floyd rm B03 improper storage
Res Life
 

05-04-05

01-19-06

03-21-06

open

open

closed

Ingles Building sprinkler system violations
Facilities
 

10-31-05

11-15-05

01-19-06

open

open

closed

Ingles fire alarm panel backup batteries need replacing
Facilities
06-07867

10-31-05

11-15-05

01-19-06

01-31-06

open

open

closed

open

closed

Ingles air duct at elevator side smoke detector failed inspection
Facilities
06-07867

11-15-05

01-19-06

open

closed

Ingles sprinkler box and water heater open outlet
Facilities
06-07868

11-15-05

01-19-06

open

closed

Ingles elevator lobby ceiling finished not maintained
Facilities
06-07869

11-15-05

01-19-06

01-31-06

03-21-06

04-25-06

06-07-06

07-17-06

open

open

open

open

open

open

closed

Ingles fire alarm panel trouble light on
Facilities
06-07870

11-15-05

01-19-06

01-25-06

01-31-06

03-21-06

04-25-06

open

open

closed

open

open

closed

Ingles mech closets floors 2 & 3 wall not complete above door
Facilities
06-07871

11-15-05

01-19-06

01-25-06

01-31-06

03-21-06

open

open

closed

open

closed

Ingles rm 125 fire door not maintained
Facilities
06-07872

11-15-05

01-19-06

01-25-06

01-31-06

03-21-06

04-25-06

06-07-06

open

open

closed

open

open

open

closed

Ingles rm 323 fire door not being maintained Facilities  

11-15-05

01-19-06

open

closed

Ingles Network rm 2nd floor extension cord
Network Serv
 

11-15-05

01-19-06

01-25-06

01-31-06

03-21-06

open

open

closed

open

closed

Ingles hall at rm 111 (#9) exit sign backup out
Facilities
06-07873

02-23-05

closed Jefferson throughout building no documentation for flame resistant fabrics
Res Life
 

02-23-05

closed Jefferson

rms 311, 309, 122, 120, 113,

111

multi-plug adapters
Res Life
 

02-23-05

closed Jefferson rms 120, 108 powerstrips connected to each other
Res Life
 

02-23-05

05-04-05

closed Jefferson rm 308 powerstrips connected to each other
Res Life
 

02-23-05

closed Jefferson hall outside network services wall penetrations
Facilities
 

02-23-05

closed Jefferson rms 227, 231, 109 extension cords
Res Life
 

02-23-05

05-04-05

open

closed

Jefferson 16 rooms no weekly records for smoke detectors
Res Life
 

05-04-05

05-17-05

open

closed

Jefferson Building some smoke/heat detectors failed inspection
Facilities
14435

10-31-05

11-29-05

01-19-06

open

open

closed

Jefferson fire alarm panel backup batteries need replacing
Facilities
06-08308

11-29-05

01-19-06

01-25-06

open

open

closed

Jefferson rm123 multi plug extension cord
Res Life
 

11-29-05

01-19-06

01-25-06

open

open

closed

Jefferson building daisy chaining power taps
Res Life
 

11-29-05

01-19-06

01-31-06

03-21-06

04-25-06

open

closed

open

open

closed

Jefferson network services (telephone services?) outlets not covered
Facilities

06-08309

06-08311

11-29-05

01-19-06

01-25-06

open

open

closed

Jefferson network services openings in electrical panel
Facilities
06-08309

11-29-05

01-19-06

open

closed

Jefferson rm 110, 130 outlets not working properly
Facilities
06-08311

11-29-05

01-19-06

01-25-06

01-31-06

open

closed

open

open

closed

Jefferson res life storage rm basement penetrations not fire stopped
Facilities
06-08312

01-20-05

closed Madison rm 327 smoke detectors, no weekly records
Facilities
 

01-20-05

closed Madison rm 321 no documentation for flame resistant fabrics
Facilities
 

01-20-05

closed Madison rm 121 extension cords
Res Life
 

01-20-05

01-19-06

open

closed

Madison basement lounge stairwell fire doors do not latch automatically
Facilities
11093

05-04-05

05-17-05

open

closed

Madison Building some smoke/heat detectors failed inspection
Facilities
14436

10-31-05

12-06-05

01-19-06

open

open

closed

Madison fire alarm panel backup batteries need replacing
Facilities
06-08577

10-31-05

12-06-05

01-19-06

open

open

closed

Madison stair at rm 108 smoke detector failed inspection
Facilities
06-08577

12-06-05

01-19-06

01-25-06

open

open

closed

Madison stair near rm 228 fire door assembly not being maintained
Facilities
06-08582

12-06-05

01-19-06

01-25-06

02-14-06

open

closed

open

closed

Madison mech rm elev shaft not fire stopped
Facilities
06-08583

12-06-05

01-19-06

01-25-06

open

open

closed

Madison RU Outdoors office light fixture not mounted properly
Facilities
06-08584

12-06-05

01-19-06

01-25-06

02-14-06

04-25-06

open

open

open

open

closed

Madison Office B-15 being used as storage rm
Res Life
 

12-06-05

01-19-06

01-25-06

02-14-06

04-25-06

open

open

open

open

closed

Madison basement stair door wood paneling
Facilities
Doug

12-06-05

01-19-06

01-25-06

02-14-06

04-25-06

open

open

open

open

closed

Madison basement flame spread rating on paneling not verified
Facilities
Doug

01-20-05

closed Moffett attic fire doors do not latch automatically
Facilities
 

02-23-05

closed Moffett attic fire doors do not latch automatically
Facilities
 

04-06-05

closed Moffett E305, E316, E322, E204, W333,W209, W110 extension cords
Res Life
 

04-06-05

05-04-05

open

closed

Moffett W227, W110 extension cords
Res Life
 

04-06-05

01-19-06

open

closed

Moffett E329, W221, E228, E222, E124 powerstrips connected
Res Life
 

04-06-05

05-04-05

open

closed

Moffett W321 powerstrips connected
Res Life
 

04-06-05

closed Moffett by W328 and by W209 fire doors do not latch automatically
Facilities
14645

04-06-05

closed Moffett 21 rooms smoke detector not being tested weekly
Res Life
 

04-06-05

05-04-05

open

closed

Moffett 26 rooms smoke detector not being tested weekly
Res Life
 

04-06-05

closed Moffett

W215, E122, W119, utility

rm student health

multi plug adapters
Res Life
 

04-06-05

05-04-05

open

closed

Moffett W215 multi plug adapters
Res Life
 

05-04-05

01-19-06

open

closed

Moffett Building some smoke/heat detectors failed inspection
Facilities
14438

10-31-05

12-06-05

01-19-06

open

open

closed

Moffett fire alarm panel backup batteries need replacing
Facilities
06-08549

10-31-05

12-06-05

01-19-06

open

open

closed

Moffett hall at rm 227E smoke detector failed inspection
Facilities
06-08549

12-06-05

01-19-06

open

closed

Moffett stair student health pull station needs to be removed
Facilities
06-08549

12-06-05

01-19-06

open

closed

Moffett 3rd fl west kitchen damaged heat detector
Facilities
06-08549

12-06-05

01-19-06

open

closed

Moffett 3rd fl west vending area smoke detector not secured
Facilities
06-08549

12-06-05

01-19-06

01-25-0

02-14-06

03-21-06

04-25-06

 

open

open

open

open

open

closed

 

Moffett mech rm in health serv near stair no light fixture
Facilities
06-08550

12-06-05

01-19-06

01-25-06

open

open

closed

Moffett mech rm student health trash being stored
Facilities
06-08551

12-06-05

01-19-06

01-25-06

open

open

closed

Moffett exam rm 4 extension cords
St Health
 

12-06-05

01-19-06

open

closed

Moffett stair at E. side elev equip rm exit sign backup out
Facilities
06-08552

12-06-05

01-19-06

02-14-06

03-21-06

open

closed

open

closed

Moffett near rm E110 exit sign backup out
Facilities
06-08552

12-06-05

01-19-06

02-14-06

03-21-06

open

closed

open

closed

Moffett attic east & west elevator shaft penetrations not fire stopped
Facilities
06-08553

12-06-05

01-19-06

02-14-06

03-21-06

open

closed

open

closed

Moffett student rec rm open junction boxes
Facilities
06-08554

12-06-05

01-19-06

02-14-06

03-21-06

04-25-06

open

closed

open

open

closed

Moffett attic center section on the west end dormer open junction boxes Facilities 06-08554

12-06-05

01-19-06

01-25-06

2-14-06

03-21-06

04-25-06

open

open

open

open

open

closed

Moffett halls 1,2,3 fire door hardware not being maintained
Facilities
06-08565

12-05-05

01-19-06

01-25-06

open

open

closed

Moffett kitchen area fire ext not tagged
Res life
 

04-18-05

closed Muse Main panel panel in trouble mode
Facilities
 

04-18-05

closed Muse A1017, A902, C509, B412, B309 powerstrips connected
Res Life
 

04-18-05

closed Muse A801, A502, B109 no documentation for flame resistant fabrics
Res Life
 

04-18-05

closed Muse A701, B500, B410, C221, C231 extension cords
Res Life
 

04-18-05

closed Muse A701, A715, B410, C309 multi-plug adapters
Res Life
 

04-18-05

closed Muse A701, penthouse meeting rm damaged outlets
Facilities
 

04-18-05

closed Muse A204 trash chute door not closing
Facilities
 

04-18-05

06-09-05

07-21-05

01-19-06

open

open

open

closed

Muse 11th floor stairwell standpipe missing valve handle
Facilities
15237

04-18-05

closed Muse 4th floor stairwell by rm B412 cap missing from standpipe connection
Facilities
issued

05-04-05

01-19-06

open

closed

Muse Building some smoke/heat detectors failed inspection
Facilities
14440

10-31-05

01-19-06

open

closed

Muse fire alarm panel backup batteries need replacing
Facilities
 

10-31-05

01-19-06

open

closed

Muse rm B210, 219, C404 smoke detector failed inspection
Facilities
 
06-07-06 open Muse Building maufacturer's recalled sprinkler heads Facilities  

02-23-05

05-04-05

open

closed

Norwood 2nd floor hskp closet exposed wiring
Facilities
15807

02-23-05

01-19-06

open

closed

Norwood hall by rm 210 EM light battery backup not working
Facilities
 

05-04-05

01-19-06

open

closed

Norwood Building some smoke/heat detectors failed inspection
Facilities
14441

10-31-05

11-29-05

01-19-06

open

open

closed

Norwood fire alarm panel backup batteries need replacing
Facilities
06-08303

10-31-05

11-29-05

01-19-06

open

open

closed

Norwood rm 224 smoke detector failed inspection
Facilities
06-08303

11-29-05

01-19-06

01-31-06

03-21-06

04-25-06

open

closed

open

open

closed

Norwood door to attic fire door not latching
Facilities
06-08304

11-29-05

01-19-06

01-25-06

03-21-06

open

closed

open

closed

Norwood electrical closets floors 2,3 open penetrations
Facilities
06-08306

11-29-06

01-19-06

01-25-06

01-31-06

03-21-06

open

open

open

open

closed

Norwood 2nd floor electrical closet, basement stair door, elev equip room fire rated wall not being maintained Facilities 06-08306

11-29-05

01-19-06

01-31-06

03-21-06

04-25-06

06-07-06

open

closed

open

open

open

closed

Norwood 3rd floor stairs, rm 116, 122, 126 sprinkle heads damaged
Facilities
06-08307

11-29-05

01-19-06

01-25-06

01-31-06

03-21-06

open

open

open

open

closed

Norwood 1st floor electr equip rm storage
 

05-04-05

01-19-06

open

closed

Peery Building sprinkler system violations
Facilities
 

10-31-05

01-19-06

open

closed

Peery fire alarm panel backup batteries need replacing
Facilities
 

11-08-05

01-19-06

01-31-06

03-21-06

04-25-06

06-07-06

07-17-06

open

closed

open

open

open

open

open

Peery sprinklers inspection records not available, not being maitained according to code
Facilities
 

11-08-05

01-19-06

open

closed

Peery exit signs, emergency lights inspection records not available
Safety
 

11-08-05

01-19-06

01-26-06

01-31-06

03-22-06

04-25-06

open

open

closed

open

open

closed

Peery hskp closets 2nd and 3rd floors fire stopping not being maintained
Facilities
 

11-08-05

01-19-06

01-26-06

open

open

closed

Peery surface mounted conduit rm 205 not completed
Facilities
 

11-08-05

01-19-06

01-26-06

open

open

closed

Peery decorative materials on door of rm 114 no documentation to verify material is flame resistant
Res Life
 

11-08-05

01-19-06

01-26-06

open

open

closed

Peery fire rated door at elevator equipment rm assembly not maintained properly
Facilities
 

11-08-05

01-19-06

01-26-06

01-31-06

03-21-06

open

open

open

open

closed

Peery elevator equipment rm sprinkler piping fire stopping not complete
Facilities
06-07690

11-08-05

01-19-06

01-26-06

open

open

closed

Peery rm B10 light fixture improperly mounted
Facilities
 

11-08-05

01-19-06

01-26-06

open

open

closed

Peery crawl space improper storage
Facilities
 

01-20-05

closed Pokie equipment room in basement open wiring
Facilities
 

05-04-05

01-19-06

open

closed

Pokie Building some smoke/heat detectors failed inspection
Facilities
14442

10-31-05

11-15-05

01-19-06

open

open

closed

Pokie fire alarm panel backup batteries need replacing
Facilities
06-07861

10-31-05

01-19-06

open

closed

Pokie 1st floor lounge smoke detector failed inspection
Facilities
 

11-15-05

01-19-06

open

closed

Pokie exit sign near rm 205 backup out
Facilities
06-07862

11-15-05

01-19-06

open

closed

Pokie Study Lounge basement damaged outlet
Facilities
06-07863

01-20-05

05-04-05

open

closed

Stuart 1st floor near rm 109 fire doors do not latch automatically
Facilities
11092

02-23-05

closed Stuart by room 109 fire doors do not latch automatically
Facilities
 

01-20-05

closed Stuart rm 119 powerstrips connected to each other
Res Life
 

05-04-05

01-19-06

open

closed

Stuart Building sprinkler system violations
Facilities
 

10-31-05

01-19-06

open

closed

Stuart fire alarm panel backup batteries need replacing
Facilities
 

10-31-05

01-19-06

open

closed

Stuart hall at rm 217 smoke detector failed inspection
Facilities
 

11-08-05

01-19-06

01-31-06

03-21-06

open

closed

open

closed

Stuart sprinklers inspection records not available
Facilities
 

11-08-05

01-19-06

open

closed

Stuart exit signs, emergency lights inspection records not available
Facilities
 

11-08-05

01-19-06

01-26-06

03-21-06

open

closed

open

closed

Stuart sprinkler top of stairs painted
Facilities
06-07696

11-08-05

01-19-06

01-26-06

03-21-06

open

closed

open

closed

Stuart hall rm 317 ceiling not maintained
Facilities
06-07696

11-08-05

01-19-06

open

closed

Stuart exit sign in hall near rm 220 damaged
Facilities
 

11-08-05

01-19-06

01-26-06

open

open

closed

Stuart exit sign in basement near elevator turned in wrong direction
Facilities
 

11-08-05

01-19-06

01-26-06

open

open

closed

Stuart fire doors rm 218, B01 not self closing and latching
Facilities
 

11-08-05

01-19-06

01-26-06

01-31-06

03-21-06

04-25-06

open

closed

open

open

open

closed

Stuart surface mounted conduit rm B04 corner covers removed
Facilities
06-07700

11-08-05

01-19-06

01-26-06

01-31-06

03-21-06

04-25-06

open

open

open

closed

open

closed

Stuart light fixture rm B10 improperly mounted
Facilities
 

11-08-05

01-19-06

01-26-06

03-21-06

open

open

open

closed

Stuart crawl space unapproved storage
Facilities
06-07702

01-20-05

closed Tyler rm 368 extension cord
Res Life
 

01-20-05

closed Tyler rms 210 extension cord
Res Life
 

01-20-05

closed Tyler network rm across from rm 317, electrical rm in basement ceiling finish not maintained
Facilities
08484

01-20-05

closed Tyler rms 152, 125 no documentation for flame resistant fabrics
Res Life
 

02-23-05

01-19-06

03-21-06

closed

open

closed

Tyler network rm by rm 317 ceiling finish not maintained
Facilities
 

10-31-05

11-29-05

01-19-06

open

open

closed

Tyler fire alarm panel backup batteries need replacing
Facilities
06-08295

10-31-05

11-29-05

01-19-06

open

open

closed

Tyler rm 134, section 2 of the attic smoke detector failed inspection
Facilities
06-08259

11-29-05

01-19-06

open

closed

Tyler basement mech rm emerg light not working
Facilities
06-08296

11-29-05

01-19-06

01-25-06

01-31-06

03-21-06

04-25-06

open

open

open

open

open

closed

Tyler rm 364 open penetrations
Facilities
06-09998

11-29-05

01-19-06

01-25-06

03-21-06

open

open

open

closed

Tyler hskp closet at laundry open penetrations
Facilities
06-09998

11-29-05

01-19-06

01-25-06

01-31-06

03-21-06

04-25-06

open

open

open

open

open

closed

Tyler above hall fire rated doors all floors open penetrations Facilities 06-09998

11-29-05

01-19-06

01-25-06

01-31-06

03-21-06

04-25-06

06-07-06

07-17-06

open

closed

open

open

open

open

open

closed

Tyler electrical panels 3BSEC1 and 3BSEC2 not labeled properly
Facilities
06-08297

11-29-05

01-19-06

open

closed

Tyler basement equip rm openings in electric panel
Facilities
06-08298

11-29-05

01-19-06

01-31-06

03-21-06

04-25-06

open

closed

open

open

closed

Tyler mech equip rm ceiling open junction box
Facilities
06-08298

11-29-05

01-19-06

01-25-06

03-21-06

open

closed

open

closed

Tyler rm 216 no doc to verify decorative mat are non-combust
Res Life
 

11-29-05

01-19-06

01-25-06

01-31-06

03-21-06

04-25-06

open

open

open

open

open

closed

Tyler rm 262 storage not orderly
Res Life
 

11-29-05

01-19-06

01-25-06

03-21-06

open

closed

open

closed

Tyler fire alarm panel rm, rm 103, rm 026 ceiling finish not maintained
Facilities
06-08299

11-29-05

01-19-06

01-25-06

01-31-06

03-21-06

open

open

closed

open

closed

Tyler RD apt barrel bolt on egress door
Res Life
 

01-20-05

02-23-05

05-04-05

open

open

closed

Washington by room 206 fire doors do not latch automatically
Facilities
 

01-20-05

02-23-05

open

closed

Washington rms 333, 233, 139, 133 smoke detectors, no weekly records
Res Life
 

05-04-05

05-17-05

open

closed

Washington Building some smoke/heat detectors failed inspection
Facilities
14446

10-31-05

12-06-05

01-19-06

open

open

closed

Washington fire alarm panel backup batteries need replacing
Facilities
06-08546

10-31-05

01-19-06

open

closed

Washington B level laundry heat detector failed inspection
Facilities
 

12-06-05

01-19-06

01-24-06

open

open

closed

Washington exit signs #19, 17, 3,5,7 backup power out
Facilities
06-08547

12-06-05

01-19-06

01-24-06

open

open

closed

Washington across from rm 120 storage not orderly
Res Life
 

12-06-05

01-19-06

01-24-06

open

open

closed

Washington stair across from basement elev fire door assembly
Facilities
06-08548

12-06-05

01-19-06

02-14-06

04-26-06

06-07-06

open

open

open

open

closed

Washington basement English Dept flame spread rating on paneling not verified
 

03-23-05

 

 

702 Fairfax   no violations noted
 

03-23-05

closed 704 Fairfax Apt A smoke detector not tested weekly
Res Life
 

03-23-05

closed 714 Downey EMS fire extinguisher not inspected
 

03-23-05

closed 714 Downey EMS smoke detector missing
 

03-23-05

closed 714 Downey EMS outlet cover plate missing
Facilities
14129

03-23-05

closed 714 Downey Apt D extension cord
Res Life
 
03-23-05

closed

1015 Calhoun Apt H, J, N, M, R, C open floor/ceiling penetrations
Facilities
14126
03-23-05
closed 1015 Calhoun Apt H multi-plug adapter
Res Life
 
03-23-05
closed 1015 Calhoun Apt B,K powerstrips connected
Res Life
 
03-23-05
closed 1015 Calhoun Apt Q extension cord
Res Life
 
03-23-05
closed 1015 Calhoun Apt Q open spaces in electrical panel
Facilities
14127
03-23-05
closed 1015 Calhoun Apt A outlet cover plate missing
Facilities
14128
03-23-05
closed 1015 Calhoun Apt A smoke detector not tested weekly
Res Life
 

03-23-05

06-9-05

07-21-05

01-19-06

02-28-06

open

open

open

open

closed

Selu fire alarm panel Fire alarm panel in trouble mode
Facilities
14125 16744

10-31-05

01-19-06

02-28-06

open

open

closed

Selu fire alarm panel backup batteries need replacing
Facilities
 

10-31-05

01-19-06

02-28-06

open

open

closed

Selu upstairs top stairwell smoke detector failed inspection
Facilities